B.13 T: Motor Tuning
Enter data into the following parameters to tune the motor and drive for optimal performance. When the drive is not accessible,
the current values of these parameters are not accessible. The default values are set by the Bypass Controller when a Bypass
Control Parameter Initialize (Z1-01 = 1, 2, or 3) command is given.
u
T1: Induction Motor Auto-Tuning
No.
(Addr.
Hex)
Name
LCD Display
Description
Values
Page
T1-01
(0701)
Auto-Tuning Mode
Selection
Tuning Mode Sel
2: Term Resistance
3: On-
DelayCompTune
2: Stationary Auto-Tuning for Line-to-Line Resistance
3: Rotational Auto-Tuning for V/f Control Energy Saving
Default: 2
Range: 2, 3
T1-02
(0702)
Motor Rated Power
Mtr Rated Power
Sets the motor rated power as specified on the motor nameplate.
Note:
Use the following formula to convert horsepower
into kilowatts: 1HP = 0.746 kW.
Default:
<1>
Min.: 0.00 kW
Max.: 650.00
kW
T1-03
(0703)
Motor Rated Voltage
Rated Voltage
Sets the motor rated voltage as specified on the motor nameplate. Default: 200.0
V
<2>
Min: 0.0
Max: 255.0
<2>
T1-04
(0704)
Motor Rated Current
Rated Current
Sets the motor rated current as specified on the motor nameplate. Default:
<1>
Min.: 10% of
drive rated
current
Max.: 150% of
drive rated
current
T1-05
(0705)
Motor Base Frequency Rated Frequency
Sets the rated frequency of the motor as specified on the motor
nameplate.
Default: 60.0
Hz
Min.: 0.0
Max.: 400.0
T1-06
(0706)
Number of Motor Poles Number of Poles
Sets the number of motor poles as specified on the motor
nameplate.
Default: 4
Min.: 2
Max.: 48
T1-07
(0707)
Motor Base Speed
Rated Speed
Sets the rated speed of the motor as specified on the motor
nameplate.
Default: 1750 r/
min
Min.: 0
Max.: 14400
T1-11
(070B) Motor Iron Loss
Mtr Iron Loss(W)
Sets the iron loss for determining the Energy Saving coefficient. Default: 14 W
Min.: 0
Max.: 65535
<1> Default setting is dependent on parameter o2-04, Drive Model Selection.
<2> Values shown are specific to 208 Vac. Double the value for 480 Vac.
B.13 T: Motor Tuning
340
YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual