Main circuit terminal functions, Wire gauge and tightening torque specifications – Yaskawa Z1000U HVAC Matrix Bypass User Manual
Page 86
u
Main Circuit Terminal Functions
Table 3.1 Main Circuit Terminal Functions
Terminal
Description
Function
Page
1/L1
Main circuit power supply input
Connects line power to the bypass
2/L2
3/L3
1/T1
Drive output
Connects to the motor
2/T2
3/T3
For 208 Vac: 100 Ω or less
For 480 Vac: 10 Ω or less
Grounding terminal
u
Wire Gauge and Tightening Torque Specifications
Note:
1. For 0 to 100 A, use a minimum of 60 °C - 75 °C copper wire.
2. For above 100 A, use a minimum of 75 °C copper wire.
3. Wire gauge recommendations based on drive continuous current ratings using 75 °C 600 Vac vinyl-sheathed wire assuming ambient
temperature within 40 °C and wiring distance less than 100 m.
• Consider the amount of voltage drop when selecting wire gauges. Increase the wire gauge when the voltage drop is greater
than 2% of motor rated voltage. Ensure the wire gauge is suitable for the terminal block. Use the following formula to
calculate the amount of voltage drop:
Line drop voltage (V) = 3 × wire resistance (Ω/km) × wire length (m) × current (A) × 10
-3
•
Refer to UL Standards Compliance on page 450
for information on UL compliance.
Table 3.2 Main Input Circuit Wiring Tightening Torques and Wire Gauges With Option PW
Bypass Model Z1D1
Standard Circuit Breaker With Option PW
208 Vac
480 Vac
Current Rating (A)
Wire Size Range (AWG)
Tightening Torque (lb. in.)
–
B011
25
14-10
or
8-3/0
50
or
120
–
B014
30
–
B021
45
D024
B027
60
D030
B034
70
–
B040
80
D046
B052
110
D059
B065
125
D074
B077
150
D088
B096
D114
–
–
B124
250
4-4/0
225
D143
B156
3/0-350 kcmil
225
D169
B180
D211
–
400
(1-2) x (2/0-500 kcmil)
(1-2) x 442
–
B240
600
–
B032
–
B361
(1-3) x (3/0-500 kcmil)
(1-3) x 450
–
B414