2.2 Mechanical Installation

This section outlines specifications, procedures, and the environment for proper mechanical installation of the bypass.

u

Installation Environment

Install the bypass in an environment matching the conditions below to prolong its optimum performance life.

Table 2.1 Installation Environment

Environment

Conditions

Installation Area

Indoors

Ambient

Temperature

-10 to + 40 °C (+14 to +104 °F) NEMA Type 1 Enclosure

Humidity

95% RH or less and free of condensation

Storage

Temperature

-20 °C to +60 °C (-4 °F to +104 °F)

Surrounding Area

Install the drive in an area free from:
• oil mist and dust
• metal shavings, oil, water, or other foreign materials
• radioactive materials
• combustible materials (e.g., wood)
• harmful gases and liquids
• excessive vibration
• chlorides
• direct sunlight.

Altitude

Up to 1000 meters without derating. Up to 3000 meters with output current and voltage derating

Orientation

Install the bypass vertically to maintain maximum cooling effects.

NOTICE: Avoid placing peripheral devices, transformers, or other electronics near the bypass as the noise created can lead to erroneous

operation. If such devices must be used in close proximity to the bypass, take proper steps to shield the bypass from noise.

NOTICE: Prevent foreign matter such as metal shavings and wire clippings from falling into the bypass during installation. Failure to comply

could result in damage to the bypass. Place a temporary cover over the top of the drive during installation. Remove the temporary cover

before bypass start-up, as the cover will reduce ventilation and cause the bypass to overheat.

2.2 Mechanical Installation

70

YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual