B1-04: reverse operation selection, 2 b: application – Yaskawa Z1000U HVAC Matrix Bypass User Manual
Page 134

DC Injection Braking time is determined by the value set to b2-04 and the output frequency at the time the Run command is
removed. It can be calculated by:
DC Injection brake time
(b2-04) x 10 x Output frequency
Max. output frequency (E1-04)
=
Output frequency when
Stop command was entered
100%
(Maximum output
frequency)
10%
DC Injection braking time
b2-04×10
b2-04
Figure 5.3 DC Injection Braking Time Depending on Output Frequency
Note:
If an overcurrent (oC) fault occurs during DC Injection Braking to Stop, lengthen the minimum baseblock time (L2-03) until the fault no
longer occurs.
Setting 3: Coast with Timer
When the Run command is removed, the drive will turn off its output and the motor will coast to stop. The drive will not start
if a Run command is input before the time t (C1-02) has expired. Cycle the Run command that was activated during time t
after t has expired to start the drive.
Drive output shut off
Run wait time t
Run command
Output
frequency
ON
ON
ON
OFF
OFF
Figure 5.4 Coast with Timer
The wait time t is determined by the output frequency when the Run command is removed and by the active deceleration time.
Min output
frequency
100%
(Max output
frequency)
Output frequency
when Stop command
was entered
Run wait time t
Active deceleration time
Momentary Power Loss
Minimum Baseblock
Time (L2-03)
Figure 5.5 Run Wait Time Depending on Output Frequency
n
b1-04: Reverse Operation Selection
Enables and disables Reverse operation. For some applications, reverse motor rotation is not appropriate and may cause
problems (e.g., air handling units, pumps, etc.).
No.
Parameter Name
Setting Range
Default
b1-04
Reverse Operation Selection
0, 1
1
5.2 b: Application
134
YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual