Using the hoa keypad, Hoa keypad keys and displays, 2 using the hoa keypad – Yaskawa Z1000U HVAC Matrix Bypass User Manual
Page 111: For details on the hoa keypad

4.2 Using the HOA Keypad
Use the HOA keypad to enter OFF commands, switch AUTO or HAND Mode, change parameters, and display data including
fault and alarm information.
u
HOA Keypad Keys and Displays
F2
F1
ESC
M
M
AUTO
OFF
ENTER
RESET
ALM
DIGITAL OPERATOR JVOP-183
HAND
12
11
9
8
1
2
3
10
4
5 6
7
Figure 4.1 Description of HOA Keypad Keys and Displays
No.
Display
Name
Function
1
F1
F2
Function Key F1
(Drive Test)
Selects Drive Test Mode
Function Key F2
(Bypass/Drive)
Toggles selection between Bypass Mode and Drive Mode.
2
ESC
ESC Key
• Returns to the previous display.
• Moves the cursor one space to the left.
• In Drive Mode, repeatedly pressing this button will return to the Frequency Reference display.
• In Bypass Mode, repeatedly pressing this button will return to the UB-01 “Bypass Current” display.
• During parameter entry, allows aborting the current edited value and exits the parameter editing
mode.
3
RESET Key
• Moves the cursor to the right.
• Resets the bypass or drive to clear a fault situation.
4
AUTO
AUTO Key
Selects AUTO mode.
5
Up Arrow Key
Scrolls up to display the next item, selects parameter numbers, and increments setting values.
6
Down Arrow Key
Scrolls down to display the previous item, selects parameter numbers, and decrements setting values.
7
OFF
OFF Key
Selects OFF mode.
If the drive was operating the motor, the motor will stop according to the stopping method selected in
b1-03.
If the bypass was operating the motor, the bypass contactor opens and the motor coasts to a stop.
8
ENTER Key
• Enters parameter values and settings.
• Selects a menu item to move between displays.
9
HAND
HAND Key
Selects HAND mode.
10
AUTO
AUTO Light
Lit while the drive is in AUTO mode. Refer to page
11
HAND
HAND Light
Lit while the drive is in HAND mode. Refer to page
for details.
12
ALM LED Light
Flashing: Indicates Alarm (minor fault)
Solid: Indicates Fault (major fault)
4.2 Using the HOA Keypad
YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual
111
4
Start-Up Programming & Operation