Setting 6: pump (secondary) application, Setting 7: pump with pid control application – Yaskawa Z1000U HVAC Matrix Bypass User Manual
Page 125

u
Setting 6: Pump (Secondary) Application
Table 4.12 Pump (Secondary): Parameter Settings
No.
Parameter Name
Default Setting
b1-04
Reverse Operation Selection
1: Reverse operation disabled
C1-01
Acceleration Time 1
20 s
d2-03
Master Speed Reference Lower Limit
20%
L5-01
Number of Auto Restart Attempts
10
L6-01
Stall Prevention Selection during Deceleration
5: UL3 at speed agree (Alarm)
u
Setting 7: Pump with PID Control Application
Table 4.13 Pump with PID Control: Parameter Settings
No.
Parameter Name
Default Setting
b1-04
Reverse Operation Selection
1: Reverse operation disabled
b5-01
PID Function Setting
1: Enabled (PID output becomes output frequency reference)
b5-03
Integral Time Setting (I)
15 s
b5-08
PID Primary Delay Time Constant
10.0 s
b5-13
PID Feedback Low Detection Level
2%
b5-14
PID Feedback Low Detection Time
25 s
b5-15
PID Sleep Function Start Level
72%
b5-16
PID Sleep Delay Time
25.5 s
C1-01
Acceleration Time 1
20 s
d2-03
Master Speed Reference Lower Limit
20%
L5-01
Number of Auto Restart Attempts
10
L6-01
Stall Prevention Selection during Deceleration
5: UL3 at speed agree (Alarm)
4.5 Application Selection
YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual
125
4
Start-Up Programming & Operation