Three-phase 480 vac models b096 to b414 – Yaskawa Z1000U HVAC Matrix Bypass User Manual
Page 302

u
Three-Phase 480 Vac Models B096 to B414
Table A.3 Power Ratings Continued (Three-Phase 480 V)
Item
Specification
Bypass Model Z1D1
B096
B124
B156
B180
B240
B302
B361
B0414
Maximum
Applicable
Motor
Capacity
<1>
HP
75
100
125
150
200
250
300
350
Input
Input Current (A)
<2>
88
114
143
165
219
276
330
378
Rated Voltage
Rated Frequency
Three-phase 480 Vac 50/60 Hz
Allowable Voltage Fluctuation
-15 to 10%
Allowable Frequency Fluctuation
±5%
Output
Rated Output Current (A)
96.0
<3>
124
<3>
156
<3>
180
<3>
240
<3>
302
<3>
361
<3>
414
<3>
Overload Tolerance
120% of rated output current for 60 s
150% peak
Carrier Frequency
User adjustable between 4 and 10 kHz
(Maximum Frequency varies with Rated Output Capacity)
Maximum Output Voltage (V)
Three-phase 480 V
Maximum Output Frequency (Hz)
400 Hz
EMC
Filter (IEC/EN 61800-3 Category 2)
Built-in
<1> The motor capacity (HP) refers to an NEC Table 430.250 208 V motor. The rated output current of the drive output amps should be equal to or
greater than the motor current. Select the appropriate capacity drive if operating the motor continuously above motor nameplate current.
<2> Assumes operation at the rated output current. Input current rating varies depending on the power supply transformer, input reactor, wiring
connections, and power supply impedance.
<3> Carrier frequency is set to 4 kHz. Current derating is required to raise the carrier frequency.
A.1 Power Ratings
302
YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual