B.16 Defaults by Drive Model
The following tables show parameters and default settings that change with the drive model selection (o2-04).
Table B.3 200 V Class Drives Default Settings by Drive Model Selection
No.
Name
Unit
Default Settings
–
Drive Model
–
2o0028
2o0042
2o0054
2o0068
o2-04
Drive Model Selection
Hex.
6A
6B
6D
6E
b3-04
V/f Gain during Speed Search
%
100
100
100
100
b3-06
Output Current 1 during Speed Search
–
0.5
0.5
0.5
0.5
b3-08
Current Control Gain during Speed Search
(Speed Estimation Type)
–
0.5
0.5
0.5
0.5
C6-02
Carrier Frequency Selection
–
1
1
1
1
E2-01
Motor Rated Current
A
26.6
39.7
53
65.8
E2-03
Motor No-Load Current
A
8
11.2
15.2
15.7
L2-02
Momentary Power Loss Ride-Thru Time
s
0.8
0.9
1
1
L2-03
Momentary Power Loss Minimum Baseblock
Time
s
0.3
0.3
0.6
0.6
L8-02
Overheat Alarm Level
°C
130
130
130
130
L8-38
Carrier Frequency Reduction Selection
–
1
1
1
1
Table B.4 200 V Class Drives Default Settings by Drive Model Selection
No.
Name
Unit
Default Settings
–
Drive Model
–
2o0081
2o0104
2o0130
2o0154
2o0192
2o0248
o2-04
Drive Model Selection
Hex.
6F
70
72
73
74
75
b3-04
V/f Gain during Speed Search
%
100
80
80
80
80
80
b3-06
Output Current 1 during Speed Search
–
0.5
0.5
0.5
0.5
0.5
0.7
b3-08
Current Control Gain during Speed
Search
(Speed Estimation Type)
–
0.5
0.5
0.5
0.5
0.5
0.5
C6-02
Carrier Frequency Selection
–
1
1
1
1
1
1
E2-01
Motor Rated Current
A
77.2
105
131
160
190
260
E2-03
Motor No-Load Current
A
18.5
21.9
38.2
44
45.6
72
L2-02
Momentary Power Loss Ride-Thru
Time
s
1
1.1
1.1
1.2
1.3
1.5
L2-03
Momentary Power Loss Minimum
Baseblock Time
s
0.6
0.6
0.6
1
1
1
L8-02
Overheat Alarm Level
°C
130
130
130
130
130
130
L8-38
Carrier Frequency Reduction
Selection
–
1
1
1
1
1
1
Table B.5 400 V Class Drives Default Settings by Drive Model Selection
No.
Name
Unit
Default Settings
–
Drive Model
–
4o0011
4o0014
4o0021
4o0027
o2-04
Drive Model Selection
Hex.
95
97
99
9A
b3-04
V/f Gain during Speed Search
%
100
100
100
100
b3-06
Output Current 1 during Speed Search
–
0.5
0.5
0.5
0.5
b3-08
Current Control Gain during Speed Search
(Speed Estimation Type)
–
0.5
0.5
0.5
0.5
C6-02
Carrier Frequency Selection
–
1
1
1
1
E2-01
Motor Rated Current
A
7
9.8
13.3
19.9
E2-03
Motor No-Load Current
A
2.3
2.6
4
5.6
L2-02
Momentary Power Loss Ride-Thru Time
s
0.6
0.7
0.8
0.9
L2-03
Momentary Power Loss Minimum Baseblock
Time
s
0.3
0.3
0.3
0.3
L8-02
Overheat Alarm Level
°C
130
130
130
130
L8-38
Carrier Frequency Reduction Selection
–
1
1
1
1
B.16 Defaults by Drive Model
358