Examples of sequence timers – Yaskawa Z1000U HVAC Matrix Bypass User Manual
Page 201

Setting 0: Digital Output Only
Setting 1: Run
Setting 2: Run - PID Disable
n
S2-05/S2-10/S2-15/S2-20: Sequence Timers 1/2/3/4 Reference Source
Selects the frequency reference source used for running the drive when sequence timers 1 to 4 are active (only applicable when
S2-04/S2-09/S2-14/S2-19 are set to 1 or 2).
No.
Name
Setting Range
Default
S2-05
Sequence Timer 1 Reference Source
0 to 5
0
S2-10
Sequence Timer 2 Reference Source
0 to 5
0
S2-15
Sequence Timer 3 Reference Source
0 to 5
0
S2-20
Sequence Timer 4 Reference Source
0 to 5
0
Setting 0: Operator (d1-01)
Setting 1: Operator (d1-02)
Setting 2: Operator (d1-03)
Setting 3: Operator (d1-04)
Setting 4: Terminals
Setting 5: Serial Communication
u
Examples of Sequence Timers
n
Sequence Timer Example 1
Set the parameters as shown in
to accomplish the timer sequencing in
Table 5.24 Sequence Timer Example 1 Parameter Settings
No.
Name
Setting
Comment
S2-01
Sequence Timer 1 Start Time
05:00
S2-02
Sequence Timer 1 Stop Time
15:00
S2-03
Sequence Timer 1 Day Selection
2
Mon to Fri
S2-04
Sequence Timer 1 Selection
1
Run
S2-05
Sequence Timer 1 Reference Source
0
Operator (d1-01)
S2-06
Sequence Timer 2 Start Time
19:00
S2-07
Sequence Timer 2 Stop Time
22:00
S2-08
Sequence Timer 2 Day Selection
2
Mon to Fri
S2-09
Sequence Timer 2 Selection
2
Run PID Disable
S2-10
Sequence Timer 2 Reference Source
1
Operator (d1-02)
S2-11
Sequence Timer 3 Start Time
06:00
S2-12
Sequence Timer 3 Stop Time
14:00
S2-13
Sequence Timer 3 Day Selection
3
Sat to Sun
S2-14
Sequence Timer 3 Selection
1
Run
S2-15
Sequence Timer 3 Reference Source
2
Operator (d1-03)
S2-16
Sequence Timer 4 Start Time
17:00
S2-17
Sequence Timer 4 Stop Time
21:00
S2-18
Sequence Timer 4 Day Selection
10
Sun
S2-19
Sequence Timer 4 Selection
0
Digital Output Only
S2-20
Sequence Timer 4 Reference Source
0
n/a
5.11 S: Special Parameters
YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual
201
5
Programming