Yaskawa Z1000U HVAC Matrix Bypass User Manual
Page 401

Register No.
Contents
00C8H
Alarm Contents 2
bit 0
Control Circuit Undervoltage (Uv)
bit 1
Control Circuit Overvoltage (ov)
bit 2
Heatsink Overheat (oH)
bit 3
Heatsink Overheat Warning (oH2)
bit 4
Overtorque Detection 1 (oL3)
bit 5
Overtorque Detection 2 (oL4)
bit 6
Forward/Reverse Run Commands Input Error (EF)
bit 7
Baseblock (bb)
bit 8
External Fault 3, input terminal S3 (EF3)
bit 9
External Fault 4, input terminal S4 (EF4)
bit A
External Fault 5, input terminal S5 (EF5)
bit B
External Fault 6, input terminal S6 (EF6)
bit C
External Fault 7, input terminal S7 (EF7)
bit D
External Fault 8, input terminal S8 (EF8)
bit E
Fan Fault (FAn)
bit F
Overspeed (oS)
00C9H
Alarm Contents 3
bit 0
Speed Deviation (dEv)
bit 1
PG Disconnect (PGo)
bit 2
External Digital Operator Connection Fault (oPr)
bit 3
MEMOBUS/Modbus Communication Error (CE)
bit 4
Option Communication Error (bUS)
bit 5
Serial Communication Transmission Error (CALL)
bit 6
Motor Overload (oL1)
bit 7
Overload (oL2)
bit 8
Reserved
bit 9
Option Card External fault (EF0)
bit A
Motor Switch during Run (rUn)
bit B
Reserved
bit C
Serial Communication Transmission Error (CALL)
bit D
Undertorque Detection 1 (UL3)
bit E
Undertorque Detection 2 (UL4)
bit F
MEMOBUS/Modbus Communication Test Mode Error (SE)
00CAH
Alarm Contents 4
bit 0
Reserved
bit 1
Motor Overheat Alarm (PTC Input) (oH3)
bit 2 to 5
Reserved
bit 6
PID Feedback Loss (FbL)
bit 7
Excessive PID Feedback (FbH)
bit 9
Drive Disabled (dnE)
bit A
PG Disconnect (PGo)
bit B to F
Reserved
D.9 MEMOBUS/Modbus Data Table
YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual
401
D
MEMOBUS/Modbus Communications