Device object – Yaskawa Z1000U HVAC Matrix Bypass User Manual
Page 374

Object ID
Object Name
Modbus
Address
Active Text
Inactive Text
PV Access
BV67
BYP Auto Select CMD
8400H: bit 10
ON
OFF
C
BV68
Not Used BV68
8400H: bit 11
ON
OFF
C
BV69
BYP BYPASS Sel CMD
8400H: bit 12
BYP
DRV
C
BV70
BYP Fault Reset CMD
8400H: bit 13
ON
OFF
C
BV71
BYP Ext Fault CMD
8400H: bit 14
ON
OFF
C
BV72
<2>
BYP DI-01 Command
8402H: bit 0
ON
OFF
W
BV73
<2>
BYP DI-02 Command
8402H: bit 1
ON
OFF
W
BV74
<2>
BYP DI-03 Command
8402H: bit 2
ON
OFF
W
BV75
<2>
BYP DI-04 Command
8402H: bit 3
ON
OFF
W
BV76
<2>
BYP DI-05 Command
8402H: bit 4
ON
OFF
W
BV77
<2>
BYP DI-06 Command
8402H: bit 5
ON
OFF
W
BV78
<2>
BYP DI-07 Command
8402H: bit 6
ON
OFF
W
BV79
<2>
BYP DI-08 Command
8402H: bit 7
ON
OFF
W
BV80
BYP HAND Mode Status
8784H: bit 0
ON
OFF
R
BV81
BYP OFF Mode Status
8784H: bit 1
ON
OFF
R
BV82
BYP AUTO Mode Status
8784H: bit 2
ON
OFF
R
BV83
BYP DRV Mode Status
8784H: bit 3
ON
OFF
R
BV84
BYP BYPASS Mode Stat
8784H: bit 4
ON
OFF
R
BV85
BYP Smk Prg BYP Stat
8784H: bit 5
ACTIVE
OFF
R
BV86
BYP Smk Prg DRV Stat
8784H: bit 6
ACTIVE
OFF
R
BV87
BYP Safety Status
8784H: bit 7
OPEN
CLOSED
R
BV88
BYP BAS Interlk Stat
8785H: bit 0
OPEN
CLOSED
R
BV89
BYP RUN Status
8785H: bit 1
RUN
OFF
R
BV90
BYP Fault Status
8785H: bit 2
FAULT
OFF
R
BV91
BYP Auto Xfer Status
8785H: bit 3
ACTIVE
OFF
R
BV92
BYP Remote Xfer Stat
8785H: bit 4
ACTIVE
OFF
R
BV93
BYP Energy Save Stat
8785H: bit 5
ACTIVE
OFF
R
BV94
BYP Motor 1 Sel Stat
8785H: bit 6
SELECT
OFF
R
BV95
BYP Motor 2 Sel Stat
8785H: bit 7
SELECT
OFF
R
BV96
BYP Drive Flt Status
8786H: bit 0
FAULT
OFF
R
BV97
BYP Safety Flt Stat
8786H: bit 1
FAULT
OFF
R
BV98
BYP BAS ILock Status
8786H: bit 2
FAULT
OFF
R
BV99
BYP Ext Fault Stat
8786H: bit 3
FAULT
OFF
R
BV100
Not Used BV100
8786H: bit 4
FAULT
OFF
R
BV101
BYP Motor OL Stat
8786H: bit 5
FAULT
OFF
R
BV102
BYP Motor 1 OL Stat
8786H: bit 6
FAULT
OFF
R
BV103
BYP Mtr 2 OL Stat
8786H: bit 7
FAULT
OFF
R
BV104
BYP Input Phase Loss
8787H: bit 0
FAULT
OFF
R
BV105
BYP Drive Comms
8787H: bit 2
FAULT
OFF
R
BV106
BYP Loss Of Load
8787H: bit 5
FAULT
OFF
R
BV107
BYP Option Brd Comms
8787H: bit 3
FAULT
OFF
R
<1>
Refer to Accessing Bypass Parameters and the Enter Command on page 376
for an explanation of how to read and write drive parameters not
listed in the analog or binary objects.
<2> Object is disabled when Z3-12 is set to 0.
u
Device Object
The Device Object fully describes the BACnet device to the network. Notable is that the Device Object Instance ID and the
Device Object Name are configurable.
C.6 BACnet Objects Supported