H2: multi-function digital outputs – Yaskawa Z1000U HVAC Matrix Bypass User Manual
Page 325

u
H2: Multi-Function Digital Outputs
No.
(Addr.
Hex)
Name
LCD Display
Description
Values
Page
H2-01
(040B)
Terminal M1-M2
function selection
(relay)
M1-M2 Func Sel
Refer to H2 Multi-Function Digital Output Settings on pages
for descriptions of setting values.
Default: 0
Range: 0 to 164
H2-02
(040C)
Terminal M3-M4
function selection
(relay)
M3/M4 Func Sel
Default: 1
Range: 0 to 164
H2-03
(040D)
Terminal MD-ME-MF
function selection
(relay)
MD/ME/MF FuncSel
Default: 2
Range: 0 to 164
H2 Multi-Function Digital Output Settings
H2-oo
Setting
Function
LCD Display
Description
Page
0
During run
During RUN 1
Closed: A Run command is active or voltage is output.
1
Zero speed
Zero Speed
Open: Output frequency is above the minimum output frequency set in E1-09.
Closed: Output frequency is below the minimum output frequency set in E1-09.
2
Speed agree 1
Fref/Fout Agree1
Closed: Output frequency equals the speed reference (plus or minus the hysteresis
set to L4-02).
3
User-set speed agree 1
Fref/Set Agree 1
Closed: Output frequency and speed reference equal L4-01 (plus or minus the
hysteresis set to L4-02).
4
Frequency detection 1
Freq Detect 1
Closed: Output frequency is less than or equal to the value in L4-01 with hysteresis
determined by L4-02.
5
Frequency detection 2
Freq Detect 2
Closed: Output frequency is greater than or equal to the value in L4-01 with
hysteresis determined by L4-02.
6
Drive ready
Drive Ready
Closed: Power up is complete and the drive is ready to accept a Run command.
7
Power supply error
Power Supply Err
Closed: DC bus voltage is below the Uv trip level set in L2-05.
8
During baseblock (N.O.) BaseBlk 1
Closed: Drive has entered the baseblock state (no output voltage).
B
Torque detection 1
(N.O.)
Trq Det 1 N.O.
Closed: An overtorque or undertorque situation has been detected.
C
Frequency reference loss Loss of Ref
Closed: Analog frequency reference has been lost.
E
Fault
Fault
Closed: Fault occurred.
F
Not Used (Through
mode)
Not Used
Set this value when using the terminal in the pass-through mode.
10
Minor fault
Minor Fault
Closed: An alarm has been triggered, or the IGBTs have reached 90% of their
expected life span.
11
Fault reset command
active
Reset Cmd Active
Closed: A command has been entered to clear a fault via the input terminals or
from the serial network.
13
Speed agree 2
Fref/Fout Agree2
Closed: When drive output frequency equals the frequency reference ±L4-04.
14
User-set speed agree 2
Fref/Set Agree 2
Closed: When the drive output frequency is equal to the value in L4-03 ±L4-04.
15
Frequency detection 3
Freq Detect 3
Closed: When the drive output frequency is less than or equal to the value in L4-03
±L4-04.
16
Frequency detection 4
Freq Detect 4
Closed: When the output frequency is greater than or equal to the value in L4-03
±L4-04.
17
Torque detection 1
(N.C.)
Trq Det 1 N.C.
Open: Overtorque or undertorque has been detected.
1A
During Reverse
Reverse Dir
Closed: Drive is running in the reverse direction.
1B
During baseblock (N.C.) BaseBlk 2
Open: Drive has entered the baseblock state (no output voltage).
1E
Restart enabled
Dur Flt Restart
Closed: An automatic restart is performed
20
Drive overheat pre-
alarm (oH)
OH Prealarm
Closed: Heatsink temperature exceeds the parameter L8-02 value, or an external
device has triggered an oH2 alarm via multi-function input H1-oo = B.
2F
Maintenance period
Maintenance
Closed: Cooling fan, electrolytic capacitors, IGBTs, or the soft charge bypass relay
may require maintenance.
B.8 H Parameters: Multi-Function Terminals
YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual
325
B
Parameter List