D: references, D1: frequency reference, D2: frequency upper/lower limits – Yaskawa Z1000U HVAC Matrix Bypass User Manual
Page 318: D3: jump frequency, B.5 d: references

B.5 d: References
Reference parameters set the various frequency reference values during operation.
u
d1: Frequency Reference
No.
(Addr.
Hex)
Name
LCD Display
Description
Values
Page
d1-01
(0280)
Frequency Reference 1 Reference 1
Sets the frequency reference for the drive. Setting units are
determined by parameter o1-03.
Default: 0.00 Hz
Min.: 0.00
Max.: 400.00
<1>
d1-02
(0281)
Frequency Reference 2 Reference 2
Sets the frequency reference for the drive. Setting units are
determined by parameter o1-03.
Default: 0.00 Hz
Min.: 0.00
Max.: 400.00
<1>
d1-03
(0282)
Frequency Reference 3 Reference 3
Sets the frequency reference for the drive. Setting units are
determined by parameter o1-03.
Default: 0.00 Hz
Min.: 0.00
Max.: 400.00
<1>
d1-04
(0283)
Frequency Reference 4 Reference 4
Sets the frequency reference for the drive. Setting units are
determined by parameter o1-03.
Default: 0.00 Hz
Min.: 0.00
Max.: 400.00
<1>
d1-17
(0292)
Jog Frequency
Reference
Jog Reference
Sets the Jog frequency reference. Setting units are determined
by parameter o1-03.
Default: 6.00 Hz
Min.: 0.00
Max.: 400.00
<1>
–
<1> Range upper limit is determined by parameters d2-01, Frequency Reference Upper Limit.
u
d2: Frequency Upper/Lower Limits
No.
(Addr.
Hex.)
Name
LCD Display
Description
Setting
Page
d2-01
(0289)
Frequency Reference
Upper Limit
Ref Upper Limit
Sets the frequency reference upper limit as a percentage of the
maximum output frequency.
Default: 100.0%
Min.: 0.0
Max.: 110.0
d2-02
(028A)
Frequency Reference
Lower Limit
Ref Lower Limit
Sets the frequency reference lower limit as a percentage of the
maximum output frequency.
Default: 0.0%
Min.: 0.0
Max.: 110.0
d2-03
(0293)
Master Speed Reference
Lower Limit
Ref1 Lower Limit
Sets the lower limit for frequency references from analog inputs
as a percentage of the maximum output frequency.
Default: 0.0%
Min.: 0.0
Max.: 110.0
u
d3: Jump Frequency
No.
(Addr.
Hex)
Name
LCD Display
Description
Values
Page
d3-01
(0294)
Jump Frequency 1
Jump Freq 1
Eliminates problems with resonant vibration of the motor/
machine by avoiding continuous operation in predefined
frequency ranges. The drive accelerates and decelerates the
motor through the prohibited frequency ranges.
Setting 0.0 disables this function.
Parameters must be set so that d3-01 ≥ d3-02 ≥ d3-03.
Default: 0.0 Hz
Min.: 0.0
Max.: 400.0
d3-02
(0295)
Jump Frequency 2
Jump Freq 2
Eliminates problems with resonant vibration of the motor/
machine by avoiding continuous operation in predefined
frequency ranges. The drive accelerates and decelerates the
motor through the prohibited frequency ranges.
Setting 0.0 disables this function.
Parameters must be set so that d3-01 ≥ d3-02 ≥ d3-03.
Default: 0.0 Hz
Min.: 0.0
Max.: 400.0
B.5 d: References
318
YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual