The Device Object Instance ID is a unique internetwork-wide numerical value. It is a 22-bit value that can range from 0 to

4,194,303. It is configurable by parameters Z3-08 and Z3-09. Any changes to these parameters will not take effect until the

power is cycled to the bypass.
The Device Object Name is a unique internetwork-wide character string. It is a 20-character string. It is writable from the

BACnet network. Any new string written will not take effect until the power is cycled to the bypass.

C.6 BACnet Objects Supported

YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual

375

C

BACnet Communications