Yaskawa Z1000U HVAC Matrix Bypass User Manual
Page 224

Setting 10: 10 Mbps
Setting 100: 100 Mbps
n
Z4-16: Timeout
Sets the Control Connection Timeout value for detection of communication loss in tenths of a second. A value of 0 disables
the connection timeout.
Example: An entered value of 100 represents 10.0 seconds.
No.
Name
Setting Range
Default
Z4-16
Timeout
0 to 300 s
0 s
n
Z4-17 to Z4-22: Scaling Factors
These parameters define scaling factors for drive monitors in the ODVA AC/DC Drive Object (Class 2AH), Instance 1, and
the attribute given below:
Speed Scale is attribute 22
Current Scale is attribute 23
Torque Scale is attribute 24
Power Scale is attribute 26
Voltage Scale is attribute 27
Time Scale is attribute 28.
No.
Parameter Name
Setting Range
Default
Z4-17
Speed Scaling
-15 to 15
0
Z4-18
Current Scaling
0
Z4-19
Torque Scaling
0
Z4-20
Power Scaling
0
Z4-21
Voltage Scaling
0
Z4-22
Time Scaling
0
n
Z4-23 to Z4-32: Dynamic Output Assembly Parameters
Parameters used in Output Assembly 116. Each parameter contains a MEMOBUS/Modbus address. The value received for
Output Assembly 116 will be written to this corresponding MEMOBUS/Modbus address. A MEMOBUS/Modbus address
value of 0 means that the value received for Output Assembly 116 will not be written to any MEMOBUS/Modbus register.
No.
Parameter Name
Setting Range
Default
Z4-23
DOA116 1
0 to FFFFH
0
Z4-24
DOA116 2
0 to FFFFH
0
Z4-25
DOA116 3
0 to FFFFH
0
Z4-26
DOA116 4
0 to FFFFH
0
Z4-27
DOA116 5
0 to FFFFH
0
Z4-28
DOA116 6
0 to FFFFH
0
Z4-29
DOA116 7
0 to FFFFH
0
Z4-30
DOA116 8
0 to FFFFH
0
Z4-31
DOA116 9
0 to FFFFH
0
Z4-32
DOA116 10
0 to FFFFH
0
n
Z4-33 to Z4-42: Dynamic Input Assembly Parameters
Parameters used in Input Assembly 166. Each parameter contains a MEMOBUS/Modbus address. The value sent for Input
Assembly 166 will be read from this corresponding MEMOBUS/Modbus address. A MEMOBUS/ Modbus address value of
0 means that the value sent for Input Assembly 166 is not defined by the user, therefore the option default register value will
be returned.
5.14 Z: Bypass Parameters
224
YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual