Enter data from the motor nameplate, 6 auto-tuning, Press to view the default setting – Yaskawa Z1000U HVAC Matrix Bypass User Manual
Page 128: Press, And to enter the motor power nameplate data in kw, Press to save the setting

Step
Display/Result
5. Save the setting by pressing
.
Entry Accepted
6. The display automatically returns to the display shown in Step 3.
DRV-OFF
T1-
01
= 3 *3*
V/f Engy Sav Tun
Tuning Mode Sel
DATA
ESC
n
Enter Data from the Motor Nameplate
After selecting the type of Auto-Tuning, enter the data required from the motor nameplate.
Note:
These instructions continue from Step 6 in “Selecting the Type of Auto-Tuning”.
Step
Display/Result
1. Press
to access the motor output power parameter T1-02.
DRV-OFF
T1-
02
= 0.75kW
(0.00 - 650.00)
“0.75kW”
Mtr Rated Power
DATA
ESC
2. Press
to view the default setting.
DRV-OFF
T1-02=
0
00.75kW
(0.00 - 650.00)
“0.75kW”
Mtr Rated Power
3. Press
F1
left
,
F2
right
,
,
, and
to enter the motor power nameplate data in
kW.
DRV-OFF
T1-02= 000.4
0
kW
(0.00 - 650.00)
“0.75kW”
Mtr Rated Power
4. Press
to save the setting.
Entry Accepted
5. The display automatically returns to the display in Step 1.
DRV-OFF
T1-
02
= 0.40kW
(0.00 - 650.00)
“0.75kW”
Mtr Rated Power
DATA
ESC
6.
Repeat Steps 1 through 5 to set the following parameters:
• T1-03, Motor Rated Voltage
• T1-04, Motor Rated Current
• T1-05, Motor Base Frequency
• T1-06, Number of Motor Poles
• T1-07, Motor Base Frequency
DRV-OFF
T1-
03
= 200.0VAC
(0.00 - 255.00)
“200.0VAC”
Rated Voltage
DATA
ESC
DRV-OFF
T1-
10
= X.XXHz
(0.00 - 20.00)
“X.XX Hz”
Mtr Rated Slip
DATA
ESC
Note:
1. For details on each setting,
Refer to T1: Parameter Settings during Induction Motor Auto-Tuning on page 129
2. To execute Stationary Auto-Tuning for line-to-line resistance only, set parameters T1-02 and T1-04.
4.6 Auto-Tuning
128
YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual