Z2: Bypass Control Input/Output
No.
(Addr.
Hex)
Name
LCD Display
Description
Values
Page
Z2-01
(8563) Digital Input 1 Function
Select
DI-1 Func Sel
0: Unused (Available for Serial Comms)
3: DRV Multi-Function Input S3 (H1-03 Setting)
4: DRV Multi-Function Input S4 (H1-04 Setting)
5: DRV Multi-Function Input S5 (H1-05 Setting)
6: DRV Multi-Function Input S6 (H1-06 Setting)
7: DRV Multi-Function Input S7 (H1-07 Setting)
7: DRV Multi-Function Input S8 (H1-08 Setting)
21: Run (AUTO Mode)
22: Run Enable (Safety)
23: Run Interlock (BAS)
24: Remote Transfer to Bypass
25: Smoke Purge Bypass Run to Destruction
26: Smoke Purge Drive Run to Destruction at Smoke Purge
Preset Speed. Bypass controller will stay in this state even if the
drive faults or is unavailable.
27: Motor OR Select (2-Motor OR function; 0/1 for Motor 1/2.
Behavior defined by Z1-11)
28: Motor AND Select (2-Motor AND function; 0/1 for 1/2
motor. If 1 motor, then look to Motor OR input for selected motor.
Behavior defined by Z1-11)
29: Motor 1 Overload Contact. When input is open, declare an
OL Fault, issue an EF0 fault to the drive, delay per EF0 Fault
Delay Time (Z1-30), and open Drive Output (K2) and Bypass
(K3) contactors.
30: Motor 2 Overload Contact. When input is open, declare an
OL Fault, issue an EF0 fault to the drive, delay per EF0 Fault
Delay Time (Z130), and open Drive Output (K2) and Bypass
(K3) contactors.
31: HAND Select
32: AUTO Select
33: DRIVE/BYPASS Select (0/1 for Drive/Bypass)
34: Fault Reset
35: External Fault (EF0)
36: External Fault (EFB)
37: Run Reverse
Default: 21
Range: 0 to 37
Z2-02
(8564) Digital Input 2 Function
Select
DI-2 Func Sel
Default: 22
Range: 0 to 37
Z2-03
(8565) Digital Input 3 Function
Select
DI-3 Func Sel
Default: 23
Range: 0 to 37
Z2-04
(8566) Digital Input 4 Function
Select
DI-4 Func Sel
Default: 24
Range: 0 to 37
Z2-05
(8567) Digital Input 5 Function
Select
DI-5 Func Sel
Default: 25
Range: 0 to 37
Z2-06
(8568) Digital Input 6 Function
Select
DI-6 Func Sel
Default: 0
Range: 0 to 37
Z2-07
(8569)
Digital Input 7 Function
Select
DI-7 Func Sel
Default: 0
Range: 0 to 37
Z2-08
(856A) Digital Input 8 Function
Select
DI-8 Func Sel
Default: 29
Range: 0 to 37
Z2-09
(856B) Digital Input 1 Invert
Select
DI-1 Invert
0: Normal
1: Inverted
0: Normal. Lack of input signal = OFF
1: Inverted. Lack of input signal = ON
Default: 0
Range: 0, 1
Z2-10
(856C) Digital Input 2 Invert
Select
DI-2 Invert
0: Normal
1: Inverted
0: Normal. Lack of input signal = OFF
1: Inverted. Lack of input signal = ON
Default: 0
Range: 0, 1
Z2-11
(856D) Digital Input 3 Invert
Select
DI-3 Invert
0: Normal
1: Inverted
0: Normal. Lack of input signal = OFF
1: Inverted. Lack of input signal = ON
Default: 0
Range: 0, 1
Z2-12
(856E) Digital Input 4 Invert
Select
DI-4 Invert
0: Normal
1: Inverted
0: Normal. Lack of input signal = OFF
1: Inverted. Lack of input signal = ON
Default: 0
Range: 0, 1
Z2-13
(856F) Digital Input 5 Invert
Select
DI-5 Invert
0: Normal
1: Inverted
0: Normal. Lack of input signal = OFF
1: Inverted. Lack of input signal = ON
Default: 0
Range: 0, 1
Z2-14
(8570) Digital Input 6 Invert
Select
DI-6 Invert
0: Normal
1: Inverted
0: Normal. Lack of input signal = OFF
1: Inverted. Lack of input signal = ON
Default: 0
Range: 0, 1
Z2-15
(8571) Digital Input 7 Invert
Select
DI-7 Invert
0: Normal
1: Inverted
0: Normal. Lack of input signal = OFF
1: Inverted. Lack of input signal = ON
Default: 0
Range: 0, 1
B.15 Z: Bypass Parameters