Frequency reference

L3-14

15% of rated current

Figure 5.43 Deceleration for Current Limit

n

L3-06: Stall Prevention Level during Run

Sets the current level to trigger Stall Prevention during run. Depending on the setting of parameter L3-23, the level is

automatically reduced in the constant power range (speed beyond base speed).
The Stall Prevention level can be adjusted using an analog input.

Refer to Multi-Function Analog Input Terminal Settings

on page 178

for details.

No.

Name

Setting Range

Default

L3-06

Stall Prevention Level During Run

30 to 150

<1>

<1>

<1> The upper limit and default values are determined by parameter L8-38, Carrier Frequency Derating Selection.

u

L4: Reference Detection

These parameters set up the Loss of Frequency Reference function.

n

L4-01, L4-02: Speed Agree Detection Level and Detection Width

Parameter L4-01 sets the detection level for the digital output functions Speed agree 1, User-set speed agree 1, Frequency

detection 1, and Frequency detection 2.
Parameter L4-02 sets the hysteresis level for these functions.

No.

Name

Setting Range

Default

L4-01

Speed Agree Detection Level

0.0 to 400.0 Hz

0.0 Hz

L4-02

Speed Agree Detection Width

0.0 to 20.0 Hz

2.0 Hz

Refer to H2-01 to H2-03: Terminal M1-M2, M3-M4, and MD-ME-MF Function Selection on page 167

, Settings 2, 3, 4,

and 5.

n

L4-03, L4-04: Speed Agree Detection Level and Detection Width (+/-)

Parameter L4-03 sets the detection level for the digital output functions Speed agree 2, User-set speed agree 2, Frequency

detection 3, and Frequency detection 4.
Parameter L4-04 sets the hysteresis level for these functions.

No.

Name

Setting Range

Default

L4-03

Speed Agree Detection Level (+/-)

-400.0 to 400.0 Hz

0.0 Hz

L4-04

Speed Agree Detection Width (+/-)

0.0 to 20.0 Hz

2.0 Hz

Refer to H2-01 to H2-03: Terminal M1-M2, M3-M4, and MD-ME-MF Function Selection on page 167

, Settings 13, 14,

15, and 16.

n

L4-05: Frequency Reference Loss Detection Selection

The drive can detect a loss of an analog frequency reference from input A1, A2, or A3. Frequency reference loss is detected

when the frequency reference drops below 10% of the reference or below 5% of the maximum output frequency within 400

ms.

5.8 L: Protection Functions

186

YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual