beautypg.com

Yaskawa Z1000U HVAC Matrix Bypass User Manual

Page 241

background image

HOA Keypad Display

Fault Name

Communication Error timeout time not set

properly.

Verify the setting of the serial communications fault time (Z3-06) is set properly.

Controller is not sending data soon enough to stop

the timeout.

Verify the scan rate in the controller that is communicating with the bypass controller is proper. Adjust

as necessary.

HOA Keypad Display

Fault Name

FB15

Input Phase Loss

Cause

Possible Solutions

Bypass Mode current unbalance condition

exceeded the unbalance level limit set by Z1-50 for

the amount of time specified in Z1-51.

• Check input wiring including fuses, breakers, and connections upstream from the bypass.
• Check the motor wiring and connections.

HOA Keypad Display

Fault Name

FB16

Input Phase Rotation

Cause

Possible Solution

Incorrect phase rotation while Z1-52 is set to 2 in

Bypass Mode.

Check the sequence (phase rotation) of the input wiring to the bypass package.

HOA Keypad Display

Fault Name

FbH

Excessive PID Feedback
PID feedback input is greater than the level set to b5-36 for longer than the time set to b5-37. Set

b5-12 to 2 or 5 to enable fault detection.

Cause

Possible Solution

Parameters are set inappropriately

Check b5-36 and b5-37 settings.

Incorrect PID feedback wiring

Correct the wiring.

There is a problem with the feedback sensor

• Check the sensor on the control side.
• Replace the sensor if damaged.

HOA Keypad Display

Fault Name

FbL

PID Feedback Loss
This fault occurs when PID feedback loss detection is programmed to trigger a fault (b5-12 = 2) and

the PID feedback level is below the detection level set to b5-13 for longer than the time set to b5-14.

Cause

Possible Solution

Parameters are set inappropriately

Check b5-13 and b5-14 settings.

Incorrect PID feedback wiring

Correct the wiring.

There is a problem with the feedback sensor

• Check the sensor on the control side.
• Replace the sensor if damaged.

HOA Keypad Display

Fault Name

Fdv

Power Supply Frequency Fault
The input power supply frequency exceeded the allowable frequency fluctuation.

Cause

Possible Solution

A momentary power loss occurred.

Reset the fault.

An input power supply wiring terminal is loose.

Check for loose terminals.

The fluctuation in the voltage of the input power

supply is too large.

Increase the power supply frequency fault detection width (L2-27).

The built-in fuse is open.

Replace either the control board or the entire drive. For instructions on replacing the control board,

contact Yaskawa or your nearest sales representative.

HOA Keypad Display

Fault Name

GF

Ground Fault
• A current short to ground exceeded 50% of rated current on the output side of the drive.
• Setting L8-09 to 1 enables ground fault detection.

Cause

Possible Solution

Motor insulation is damaged

• Check the insulation resistance of the motor.
• Replace the motor.

6.4 Fault Detection

YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual

241

6

Diagnostics & Troubleshooting