Yaskawa Z1000U HVAC Matrix Bypass User Manual
Page 373
Object ID
Object Name
Modbus
Address
Active Text
Inactive Text
PV Access
BV18
Overcurrent – Gnd Flt
0021H:bit 0
OC-GF
OFF
R
BV19
Main Ckt OverVoltage
0021H:bit 1
OV
OFF
R
BV20
Drive OverLoad
0021H:bit 2
OL2
OFF
R
BV21
Drive OverHeat
0021H:bit 3
OH1-OH2
OFF
R
BV22
Fuse Blown
0021H:bit 5
PUF
OFF
R
BV23
PID Feedback Loss
0021H:bit 6
FBL
OFF
R
BV24
External Fault
0021H:bit 7
EF0-EF
OFF
R
BV25
Hardware Error
0021H:bit 8
CPF
OFF
R
BV26
Mtr Ovrld-OvrTorque
0021H:bit 9
OL1-OL3
OFF
R
BV27
OverSpeed
0021H:bit 10
OS-DEV
OFF
R
BV28
Main Ckt UnderVoltage
0021H:bit 11
UV
OFF
R
BV29
MCU Cntl Pwr Sy Err
0021H:bit 12
UV1-2-3
OFF
R
BV30
Output Phase Loss
0021H:bit 13
LF
OFF
R
BV31
Communication Error
0021H:bit 14
CE
OFF
R
BV32
Operator Disconnect
0021H:bit 15
OPR
OFF
R
BV33
Operating
002CH:bit 0
OPERATING
OFF
R
BV34
Zero Speed
002CH:bit 1
ON
OFF
R
BV35
Frequency Agree
002CH:bit 2
ON
OFF
R
BV36
Desired Freq Agree
002CH:bit 3
ON
OFF
R
BV37
Frequency Detect 1
002CH:bit 4
ON
OFF
R
BV38
Frequency Detect 2
002CH:bit 5
ON
OFF
R
BV39
Drv Startup Complete
002CH:bit 6
ON
OFF
R
BV40
Low Voltage Detect
002CH:bit 7
ON
OFF
R
BV41
Base Block
002CH:bit 8
ON
OFF
R
BV42
Frequency Ref Mode
8785H:bit 8
COM
LOCAL
R
BV43
Run Command Mode
8485H:bit 9
COM
LOCAL
R
BV44
Over Torque Detect
002CH:bit 11
ON
OFF
R
BV45
Frequency Ref Lost
002CH:bit 12
ON
OFF
R
BV46
Retry Error
002CH:bit 13
ON
OFF
R
BV47
Modbus Comms Error
002CH:bit 14
ON
OFF
R
BV48
Modbus Timeout Error
002CH:bit 15
ON
OFF
R
BV49
CRC Error
003DH:bit 0
ON
OFF
R
BV50
Invalid Data Length
003DH:bit 1
ON
OFF
R
BV51
Parity Error
003DH:bit 3
ON
OFF
R
BV52
Overrun Error
003DH:bit 4
ON
OFF
R
BV53
Framing Error
003DH:bit 5
ON
OFF
R
BV54
Timeout Error
003DH:bit 6
ON
OFF
R
BV55
<1>
Parameter Accept
0910H:bit 0
ON
OFF
W
BV56
<1>
Parameter Enter
0900H:bit 0
ON
OFF
W
BV57
Drive Comms Error
002CH:bit 15
ON
OFF
R
BV58
BYP Run Fwd CMD
8400H: bit 0
ON
OFF
C
BV59
BYP Run Rev CMD
8400H: bit 1
ON
OFF
C
BV60
Not Used BV60
–
ON
OFF
R
BV61
BYP Xfer to BYP CMD
8400H: bit 3
ON
OFF
C
BV62
BYP Smok Prg BYP CMD
8400H: bit 4
ON
OFF
C
BV63
BYP Smok Prg DRV CMD
8400H: bit 5
ON
OFF
C
BV64
BYP Mtr OR Sel CMD
8400H: bit 6
ON
OFF
C
BV65
BYP Mtr AND Sel CMD
8400H: bit 7
ON
OFF
C
BV66
BYP Drive Select CMD
8400H: bit 9
ON
OFF
C
C.6 BACnet Objects Supported
YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual
373
C
BACnet Communications