Yaskawa Z1000U HVAC Matrix Bypass User Manual
Page 339

No.
(Addr.
Hex)
Name
LCD Display
Description
Values
Page
S2-18
(3217)
Sequence Timer 4 Day
Selection
Tmr 4 Day Sel
0: Timer disabled
1: Daily
2: Mon - Fri
3: Sat - Sun
4: Monday
5: Tuesday
6: Wednesday
7: Thursday
8: Friday
9: Saturday
10: Sunday
Sets the days for which sequence timer 4 is active.
0: Timer disabled
1: Daily
2: Mon - Fri
3: Sat - Sun
4: Monday
5: Tuesday
6: Wednesday
7: Thursday
8: Friday
9: Saturday
10: Sunday
Default: 0
Range: 0 to 10
S2-19
(3218)
Sequence Timer 4
Selection
Tmr 4 Seq Sel
0: Digital Out Only
1: Run
2: Run - PID Disable
Sets the action that occurs when sequence timer 4 is active.
0: Digital output only
1: Run
2: Run - PID disable
Default: 0
Range: 0 to 2
S2-20
(3219)
Sequence Timer 4
Reference Source
Tmr 4 Ref Source
0: Operator (d1-01)
1: Operator (d1-02)
2: Operator (d1-03)
3: Operator (d1-04)
4: Terminals
5: Serial Com
Selects the frequency reference source used for running the drive
when sequence timer 4 is active (only applicable when S2-19 is
set to 1 or 2).
0: Operator (d1-01)
1: Operator (d1-02)
2: Operator (d1-03)
3: Operator (d1-04)
4: Terminals
5: Serial communication
Default: 0
Range: 0 to 5
B.12 S: HVAC Function
YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual
339