beautypg.com

14 specifications – Yaskawa 1000 Series Drive Option - DeviceNet Technical Manual User Manual

Page 79

background image

14 Specifications

YASKAWA ELECTRIC

SIEP C730600 43B 1000-Series Option SI-N3 Technical Manual

79

14

Specifications

Table 25 Option Specifications

Items

Specifications

Model

SI-N3

SI-N3 Supported Messages

• Group 2 Server (UCMM capable).
• Explicit Messages: Fragmentation is supported. Up to 32 bytes can be input and output.
• Polled I/O Messages: Fragmentation is not supported. Up to 8 bytes can be input and output.
• Faulted Node Recovery / Offline Connection Set Messages / Automatic Device Replacement (ADR).
• Change of State Message (COS). COS can be used as an I/O Input Assembly.

I/O Assembly Instance

Input: 17 types (4~8 bytes)
Output: 18 types (4~8 bytes)

DeviceNet Specification

Conformance Level 19: Passed

DeviceNet Profile

AC Drive

Input Power

Voltage: 11~25 Vdc
Current: 40 mA

Connector Type

5-pin open-style screw connector

Physical Layer Type

Isolated Physical Layer
CAN transceiver + photocoupler

MAC ID Setting

Programmable from drive keypad or network:
MAC ID 0 to 63

Communications Speed/Baud Rate

Programmable from drive keypad or network:

• 125/250/500 kbps
• Auto Baud Rate
• Idle Mode Detect
• Heartbeat

Ambient Temperature

-10

°C to +50 °C (14 °F to 122 °F)

Humidity

95% RH or lower with no condensation

Storage Temperature

-20

°C to +60 °C (-4 °F to 140 °F) allowed for short-term transport of the product

Area of Use

Indoor (free of corrosive gas, airborne particles, etc.)

Altitude

1000 m (3280 ft.) or lower