Explicit message communications errors, Minor faults and alarms – Yaskawa 1000 Series Drive Option - DeviceNet Technical Manual User Manual
Page 74
12 Troubleshooting
74
YASKAWA ELECTRIC SIEP C730600 43B 1000-Series Option SI-N3 Technical Manual
Minor Faults and Alarms
Explicit Message Communications Errors
When there is a problem with a request message sent from the master in explicit communications, the drive will return a
response message with a service code of “94” and an error code from
as the data.
Table 20 Explicit Message Error Codes, Causes, and Possible Solutions
Digital Operator Display
Fault Name
to
oFA30 to oFA43
Option Fault (CN5-A)
Communication ID error.
Cause
Possible Solution
Option hardware fault
Replace the option. Contact Yaskawa for assistance.
Digital Operator Display
Fault Name
oFb00
Non-Compatible Option connected to drive port CN5-B
Non-compatible option is connected.
Cause
Possible Solution
Non-compatible option connected to drive port
CN5-B
Use only compatible options. Connect the SI-N3 to CN5-A. For other option connections refer
to the Installation Manual for those options.
Digital Operator Display
Fault Name
oFb02
Option Fault (CN5-B)
Two of the same option are connected simultaneously.
Cause
Possible Solution
Options AI-A3 or D1-A3 connected to the CN5-B
port while an option was connected to CN5-A
Only one of these options, AI-A3, DI-A3 or SI-
option can be connected to the drive at the
same time. The SI-N3 must be connected to CN5-A.
Digital Operator Display
Fault Name
oFc00
Non-Compatible Option connected to drive port CN5-C
Non-compatible option is connected.
Cause
Possible Solution
Non-compatible option connected to port CN5-C
Use only compatible options. Connect the SI-N3 to CN5-A. For other option connections refer
to the Installation Manual for those options.
Digital Operator Display
Fault Name
oFc02
Option Fault (CN5-C)
Two of the same options are connected simultaneously.
Cause
Possible Solution
Options AI-A3 or D1-A3 connected to the CN5-C
port while an option was connected to CN5-A
Only one of these options, AI-A3, DI-A3 or SI-
option can be connected to the drive at the
same time. The SI-N3 must be connected to CN5-A.
Digital Operator Display
Minor Fault Name
CALL
Serial Communication Transmission Error
Communication has not yet been established.
Cause
Possible Solution
Minor Fault
(H2- = 10)
Communication wiring or terminal resistor
connection is faulty. There is a short circuit, or an
option component is not connected properly
Check for wiring errors and correct the wiring.
Remove any ground shorts and reconnect loose wires.
Yes
Master-side programming error
Check communications at start-up and correct programming errors.
Damaged communication circuitry
Perform a self-diagnostics check and replace the drive if the fault continues
to occur.
Error Code
Description
Cause
Possible Solution
08FF
Service not supported
The service code is incorrect.
Correct the service code.
09FF
Invalid attribute value
The attribute is incorrect.
Correct the attribute.
0CFF
Object state conflict
Attempted to change a drive constant that
cannot be changed while the drive is running.
Stop the drive.
0EFF
Attribute not settable
Attempted to change a read-only attribute.
Correct the service code or attribute setting.
13FF
Not enough data
The data size is incorrect.
Correct the data size.
14FF
Attribute not supported
Attempted to execute a service that is not
defined for the attribute.
Correct the service code or attribute setting.