beautypg.com

Explicit message communications errors, Minor faults and alarms – Yaskawa 1000 Series Drive Option - DeviceNet Technical Manual User Manual

Page 74

background image

12 Troubleshooting

74

YASKAWA ELECTRIC SIEP C730600 43B 1000-Series Option SI-N3 Technical Manual

„

Minor Faults and Alarms

‹

Explicit Message Communications Errors

When there is a problem with a request message sent from the master in explicit communications, the drive will return a
response message with a service code of “94” and an error code from

Table 20

as the data.

Table 20 Explicit Message Error Codes, Causes, and Possible Solutions

Digital Operator Display

Fault Name

to

oFA30 to oFA43

Option Fault (CN5-A)
Communication ID error.

Cause

Possible Solution

Option hardware fault

Replace the option. Contact Yaskawa for assistance.

Digital Operator Display

Fault Name

oFb00

Non-Compatible Option connected to drive port CN5-B
Non-compatible option is connected.

Cause

Possible Solution

Non-compatible option connected to drive port
CN5-B

Use only compatible options. Connect the SI-N3 to CN5-A. For other option connections refer
to the Installation Manual for those options.

Digital Operator Display

Fault Name

oFb02

Option Fault (CN5-B)
Two of the same option are connected simultaneously.

Cause

Possible Solution

Options AI-A3 or D1-A3 connected to the CN5-B
port while an option was connected to CN5-A

Only one of these options, AI-A3, DI-A3 or SI-

††

option can be connected to the drive at the

same time. The SI-N3 must be connected to CN5-A.

Digital Operator Display

Fault Name

oFc00

Non-Compatible Option connected to drive port CN5-C
Non-compatible option is connected.

Cause

Possible Solution

Non-compatible option connected to port CN5-C

Use only compatible options. Connect the SI-N3 to CN5-A. For other option connections refer
to the Installation Manual for those options.

Digital Operator Display

Fault Name

oFc02

Option Fault (CN5-C)
Two of the same options are connected simultaneously.

Cause

Possible Solution

Options AI-A3 or D1-A3 connected to the CN5-C
port while an option was connected to CN5-A

Only one of these options, AI-A3, DI-A3 or SI-

††

option can be connected to the drive at the

same time. The SI-N3 must be connected to CN5-A.

Digital Operator Display

Minor Fault Name

CALL

Serial Communication Transmission Error
Communication has not yet been established.

Cause

Possible Solution

Minor Fault

(H2-…… = 10)

Communication wiring or terminal resistor
connection is faulty. There is a short circuit, or an
option component is not connected properly

Check for wiring errors and correct the wiring.
Remove any ground shorts and reconnect loose wires.

Yes

Master-side programming error

Check communications at start-up and correct programming errors.

Damaged communication circuitry

Perform a self-diagnostics check and replace the drive if the fault continues
to occur.

Error Code

Description

Cause

Possible Solution

08FF

Service not supported

The service code is incorrect.

Correct the service code.

09FF

Invalid attribute value

The attribute is incorrect.

Correct the attribute.

0CFF

Object state conflict

Attempted to change a drive constant that
cannot be changed while the drive is running.

Stop the drive.

0EFF

Attribute not settable

Attempted to change a read-only attribute.

Correct the service code or attribute setting.

13FF

Not enough data

The data size is incorrect.

Correct the data size.

14FF

Attribute not supported

Attempted to execute a service that is not
defined for the attribute.

Correct the service code or attribute setting.