Yaskawa 1000 Series Drive Option - DeviceNet Technical Manual User Manual

Page 70

background image

10 General Class Objects

70

YASKAWA ELECTRIC SIEP C730600 43B 1000-Series Option SI-N3 Technical Manual

1

6

Drive Mode

Drive control mode.
0: OLV
0: OLV for PM motors (Read only)
0: Advanced OLV for PM motors (Read only)
1: V/f control
2: V/f control with PG
3: CLV
3: CLV for PM motors (Read only)

{

{

Byte

0 to 3

0

1

7

Speed Actual

Actual Drive Speed
Unit is not affected by Speed Scale SS.

{

Word

3

1

8

Speed Reference

Frequency Reference
Monitors drive frequency reference.
Unit is not affected by Speed Scale SS.

{

{

Word

0

1

9

Current Actual

Actual Output Current
Monitors drive output current
Unit is 0.1 A
Unit is not affected by Current Scale CS.

{

Word

0

1

11

Torque Actual

Drive Output Torque Unit is affected by Torque
Scale TS

{

Word

0

1

12

Torque Reference/Torque
Limit

Torque Reference/Torque Limit
Sets the torque reference and torque limit. The
units are determined by the torque scale.
Sets the torque reference when using torque
control (d5-01 = 1).
Sets the torque limit when using speed control
(d5-01 = 0).
The torque reference and torque limit are disabled
when F6-06 = 0.

{

{

Word

0

1

15

Power Actual [W]

Drive Output Power Unit is affected by Power
Scale PS

{

Word

0

1

16

Input Voltage [V]

Drive Input Voltage
Unit is affected by Voltage Scale VS

{

Word

Depends on

capacity

1

17

Output Voltage [V]

Drive Output Voltage
Unit is affected by Voltage Scale VS

{

Word

0

1

18

Accel Time [ms]

Acceleration Time 1 (C1-01)
Units set in parameter C1-10.
Unit is affected by Time scale (TS).

{

{

Word

2710 h

1

19

Decel Time [ms]

Deceleration Time 1 (C1-02)
Units set in parameter C1-10.
Unit is affected by Time scale (TS).

{

{

Word

2710 h

1

20

Low Speed Limit Percent
of Max Speed

Frequency Reference Lower Limit (d2-02)

{

{

Word 0 to 1100

0

1

21

High Speed Limit Percent
of Max Speed

Frequency Reference Upper Limit (d2-01)

{

{

Word 0 to 1100

3E8h

1

22

Speed Scale (–15 to 15)

Setting for F6-56, scale of units for speed-related
data

{

{

Byte

–15 to 15

0

1

23

Current Scale (–15 to 15)

Setting for F6-57, scale of units for current-related
data

{

{

Byte

–15 to 15

0

1

24

Torque Scale (–15 to 15)

Setting for F6-58, scale of units for torque-related
data

{

{

Byte

–15 to 15

0

1

26

Power Scale (–15 to 15)

Setting for F6-59, scale of units for power-related
data

{

{

Byte

–15 to 15

0

1

27

Voltage Scale (–15 to 15)

Setting for F6-60, scale of units for voltage-related
data

{

{

Byte

–15 to 15

0

1

28

Time Scale (–15 to 15)

Setting for F6-61, scale of units for speed-related
data

{

{

Byte

–15 to 15

0

1

29

Reference from Net
(Status)

Status of reference command from DeviceNet
0: Reference command from DeviceNet
1: Reference command from except for DeviceNet

{

Byte

0

Instance

ID

Attribute

Name

Description

Get Set Size

Range

Default