8 Output Assemblies (Drive Consumes)

YASKAWA ELECTRIC

SIEP C730600 43B 1000-Series Option SI-N3 Technical Manual

29

Note: This is a paired assembly (105/155).

Table 9 Function Code Decode Table

Note: Refer to the MEMOBUS/Modbus Data Table in the drive Technical Manual for a list of monitor data using the MEMOBUS/

Modbus message area.

Multi-Function Input 7

Terminal S7 Function Input
0: Terminal S7 Function (H1-07) OFF
1: Terminal S7 Function (H1-07) ON

Multi-Function Input 8

Terminal S8 Function Input
0: Terminal S8 Function (H1-08) OFF
1: Terminal S8 Function (H1-08) ON

External Fault

External Fault EF0
0: No External Fault (EF0)
1: External Fault (EF0)

Fault Reset

Fault Reset
0: No Fault Reset
1: Fault Reset

Function Code

MEMOBUS/Modbus Function Code

Refer to Function Code Decode Table on page 29

.

Multi-Function Digital Output

Terminal M1/M2
0: M1/M2 OFF
1: M1/M2 ON
This function is enabled only when H2-01 is set to F.

Multi-Function Photocoupler 1

Terminal P1
0: P1 OFF
1: P1 ON
This function is enabled only when H2-02 is set to F.

Multi-Function Photocoupler 2

Terminal P2
0: P2 OFF
1: P2 ON
This function is enabled only when H2-03 is set to F.

Speed Reference

Speed Command
Sets drive speed reference
Unit depends on o1-03.
Unit is not affected by Speed Scale SS.

Register Number

MEMOBUS/Modbus Register Number

<1>

Register Data

MEMOBUS/Modbus Register Data

<1> Register numbers 0x0001, 0x0002, and 0x0009 are disabled.

Function Code

High Byte - Low Byte

MEMOBUS/Modbus Function

0 0

No Operation

1 0

Read Register

0 1

Write Register

1 1

No Operation

Name

Description