beautypg.com

Yaskawa 1000 Series Drive Option - DeviceNet Technical Manual User Manual

Page 51

background image

9 Input Assemblies (Drive Produces)

YASKAWA ELECTRIC

SIEP C730600 43B 1000-Series Option SI-N3 Technical Manual

51

‹

Standard Status 2 (Vendor Specific Yaskawa Electric (YE) Assy) -152 (0x98)

ALARM

Drive Alarm
0: No Drive Alarm
1: Alarm

FAULT

Drive Fault
0: No Drive Fault
1: Fault

oPE

oPE Fault
0: No oPExx Fault
1: oPExx

Uv

Undervoltage
0: No Undervoltage
1: Undervoltage

LOCAL/REMOTE

Status of Run command from Network
0: Run command is not from network
1: Run command is from network

Multi-Function Digital Output

Terminal M1/M2
0: Terminal M1/M2 OFF
1: Terminal M1/M2 ON

Multi-Function Photocoupler 1

Terminal P1
0: Terminal P1 OFF
1: Terminal P1 ON

Multi-Function Photocoupler 2

Terminal P2
0: Terminal P2 OFF
1: Terminal P2 ON

Output Frequency

Actual Drive Speed
Monitors drive output frequency
Unit depends on o1-03.
Unit is not affected by Speed Scale SS.

Actual Torque

Output Torque
Shows the torque reference.
Value displays in 0.1% units.

Actual Current

Actual Output Current
Monitors drive output current
Unit is 0.1 A
Unit is not affected by Current Scale CS.

Input

Instance

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

152

0

FAULT

ALARM

READY

Speed
Agree

Reset

REV

Running

ZSP

Running

1

Multi-

Function

Photocoupler 2

Multi-

Function

Photocoupler 1

Multi-

Function

Digital Output

LOCAL/

REMOTE

Uv

oPE

2

Output Frequency (Low Byte)

3

Output Frequency (High Byte)

4

Speed Reference (Low Byte)

5

Speed Reference (High Byte)

6

Actual Current (Low Byte)

7

Actual Current (High Byte)

Parameter

Data

Running

Running
0: Stop
1: Forward or Reverse Running

ZSP

Zero Speed
0: Running
1: Stop or DC Injection Braking

Parameter

Data