8 Output Assemblies (Drive Consumes)
YASKAWA ELECTRIC
SIEP C730600 43B 1000-Series Option SI-N3 Technical Manual
37
Speed Dynamic Assy (Vendor Specific Yaskawa Electric (YE) Assy) - 124 (0x7C)
Note: This is a paired assembly (124/134).
Table 10 Service Code Decode Table
Output Instance
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
124
0
Multi-
Function
Input 8
Multi-
Function
Input 7
Multi-
Function
Input 6
Multi-
Function
Input 5
Multi-
Function
Input 4
Multi-
Function
Input 3
Run
Rev
Run
Fwd
1
Service Code
2
Class
3
Attribute
4
Data (Low Byte)
5
Data (High Byte)
6
Speed Reference (Low Byte)
7
Speed Reference (High Byte)
Parameter
Data
Run Fwd
Forward Run Command
0: Stop
1: Forward Run
Run Rev
Reverse Run Command
0: Stop
1: Reverse Run
Multi-Function Input 3
Terminal S3 Function Input
0: Terminal S3 Function (H1-03) OFF
1: Terminal S3 Function (H1-03) ON
Multi-Function Input 4
Terminal S4 Function Input
0: Terminal S4 Function (H1-04) OFF
1: Terminal S4 Function (H1-04) ON
Multi-Function Input 5
Terminal S5 Function Input
0: Terminal S5 Function (H1-05) OFF
1: Terminal S5 Function (H1-05) ON
Multi-Function Input 6
Terminal S6 Function Input
0: Terminal S6 Function (H1-06) OFF
1: Terminal S6 Function (H1-06) ON
Multi-Function Input 7
Terminal S7 Function Input
0: Terminal S7 Function (H1-07) OFF
1: Terminal S7 Function (H1-07) ON
Multi-Function Input 8
Terminal S8 Function Input
0: Terminal S8 Function (H1-08) OFF
1: Terminal S8 Function (H1-08) ON
Service Code
Service Code
Refer to Service Code Decode Table on page 37
Class
Class
Valid Classes are Control Supervisor Object (41) and AC/DC Object (42).
Instance will always be 1.
Attribute
Attribute
Data
Data
Speed Reference
Speed Command
Sets drive speed reference
Unit depends on o1-03.
Unit is not affected by Speed Scale SS.
Service Code
Function
0x00
No Operation
0x0E
Get Attribute Single
0x10
Set Attribute Single