beautypg.com

Option led display, Power-up diagnostics – Yaskawa 1000 Series Drive Option - DeviceNet Technical Manual User Manual

Page 10

background image

4 Option Components

10

YASKAWA ELECTRIC SIEP C730600 43B 1000-Series Option SI-N3 Technical Manual

‹

Option LED Display

The option has two bicolor, red/green LEDs: one for Module Status (MS) and one for Network Status (NS).

The operational states of the LEDs after completion of the DeviceNet power-up diagnostic LED sequence are described
in

Table 4

. Wait at least 2 seconds for the power-up diagnostic process to complete before verifying the states of the

LEDs.

Table 3 Option LED States

„

Power-Up Diagnostics

An LED test is performed each time the drive is powered up. The initial boot sequence may take several seconds. The
option is successfully initialized when the LEDs complete the diagnostic LED sequence. The LEDs then assume
operational conditions shown in

Table 3

.

Table 4 Power-Up Diagnostic LED Sequence

Name

Display

Operating Status

Remarks

Color

Status

MS

OFF

Power supply OFF

Power is not being supplied to the drive.

Green

ON

Option operating

The option is operating normally.

Green

Flashing Option initializing

There is an incorrect baud rate setting or there is a MAC ID.

Red ON

Fatal

error

occurred

A

fatal (irrecoverable) error occurred in the option.

Red Flashing

Non-fatal error occurred

A non-fatal (recoverable) error occurred.

Green/Red

Flashing

Device self-test

Device in self-test mode.

NS

OFF

Offline or Power supply OFF

Green ON

Online

communications

established

Device is on-line and has connections in the established state.

Green

Flashing

Online communications not
established

Device is on-line but has no connections in the established state.
Duplicate MAC ID test has been passed and is on-line but has no
open connections to other nodes.

Red ON

Communications

error

An error occurred disabling DeviceNet communications.

• MAC ID duplication
• Bus off detected

Red Flashing

Communications time-out

A communications time-out occurred with the master.

Green/Red

Flashing

Communication faulted

Specific communication faulted device.

• The device has detected a network access error and is in the

communications faulted state.

• The device has then received and accepted an Identify

communication fault request-long protocol message.

Sequence

Module Status (MS)

Network Status (NS)

Time (ms)

1

Green

OFF

250

2

Red

OFF

250

3

Green

Green

250

4

Green

Red

250

5

Green

OFF

-