beautypg.com

Yaskawa 1000 Series Drive Option - DeviceNet Technical Manual User Manual

Page 56

background image

9 Input Assemblies (Drive Produces)

56

YASKAWA ELECTRIC SIEP C730600 43B 1000-Series Option SI-N3 Technical Manual

‹

Standard DI/DO Status (Vendor Specific Yaskawa Electric (YE) Assy) - 157 (0x9D)

Input

Instance

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

157

0

FAULT

ALARM

READY

Speed
Agree

Reset

REV

Running

ZSP

Running

1

LOCAL/

REMOTE

Uv

oPE

2

Multi-

Function

Input 8

Multi-

Function

Input 7

Multi-

Function

Input 6

Multi-

Function

Input 5

Multi-

Function

Input 4

Multi-

Function

Input 3

Multi-

Function

Input 2

Multi-

Function

Input 1

3

Multi-

Function

Photocoupler

2

Multi-

Function

Photocoupler

1

Multi-

Function

Digital
Output

4

Analog Input 1 (Low Byte)

5

Analog Input 1 (High Byte)

6

Output Frequency (Low Byte)

7

Output Frequency (High Byte)

Parameter

Data

Running

Running
0: Stop
1: Forward or Reverse Running

ZSP

Zero Speed
0: Running
1: Stop or DC Injection Braking

REV Running

Reverse Running
0: Not Reverse Running
1: Reverse Running

Reset

Reset
0: No Reset
1: Reset

Speed Agree

Speed Agree
0: No Speed Agree
1: Actual speed at speed reference

READY

Drive Ready
0: Not Ready
1: Ready

ALARM

Drive Alarm
0: No Drive Alarm
1: Alarm

FAULT

Drive Fault
0: No Drive Fault
1: Fault

oPE

oPE Fault
0: No oPExx Fault
1: oPExx

Uv

Undervoltage
0: No Undervoltage
1: Undervoltage

LOCAL/REMOTE

Status of Run command from Network
0: Run command is not from network
1: Run command is from network

Multi-Function Input 1

Terminal S1
0: Terminal S1 OFF
1: Terminal S1 ON

Multi-Function Input 2

Terminal S2
0: Terminal S2 OFF
1: Terminal S2 ON