DeviceNet Option Error Codes

Table 21 DeviceNet Option Error Codes

15FF

Too much data

The data size is incorrect.

Correct the data size.

16FF

Object does not exist

An unsupported object was specified.

Correct the class or instance setting.

1FFF

Vendor specific error

Attempted to change a drive constant that
cannot be changed while the drive is running.
Attempted to change a drive constant to a
value outside of the setting range.

Stop the drive.
Specify a value that is within the setting range.

20FF

Invalid parameter

Attempted to change to a data value outside
of the setting range.

Specify a data value that is within the setting range.

Drive Error

Code

(hex)

<1>

DeviceNet

Error Code

(hex)

Description

Corrective Action

00

0000

None

-

01

5120

DC Bus Fuse Open (PUF)

Output Transistor Failure – Replace the drive

02

3220

DC Bus Undervolt (Uv1)

Input power fluctuation too large

03

5110

CTL PS Undervolt (Uv2)

Cycle drive power – Replace drive if fault continues

04

3222

MC Answerback (Uv3)

Cycle drive power – Replace drive if fault continues

05

2130

Short Circuit (SC)

Check drive wiring
Cycle drive power – Replace drive if fault continues.

06

2120

Ground Fault (GF)

Check for motor and/or cable damage

07

2300

Over Current (oC)

Check motor, motor load and acc/dec rates

08

3210

DC Bus Overvolt (ov)

Check incoming voltage
Check deceleration time

09

4200

Heatsink Overtemp (oH)

Check ambient temperature
Check drive cooling fan

0A

4210

Heatsink Max Temp (oH1)

Check drive cooling fan

0B

2220

Motor Overload (oL1)

Check the load, acc/dec and cycle times
Check motor rated current (E2-01)

0C

2200

Inv Overload (oL2)

Check the load, acc/dec and cycle times
Check drive rating

0D

2221

Overtorque Det 1 (oL3)

Check L6-02 and L6-03 settings
Check system mechanics

0E

2222

Overtorque Det 2 (oL4)

Check L6-05 and L6-06 settings
Check system mechanics

0F

7110

DynBrk Transistor (rr)

Cycle drive power – Replace drive if fault continues

10

7112

DynBrk Resistor (rH)

Check load, operating speed and deceleration time

11

9000

External Fault 3 (EF3)

Multifunction digital input set to external fault
Circuit at terminal is closed

12

9000

External Fault 4 (EF4)

13

9000

External Fault 5 (EF5)

14

9000

External Fault 6 (EF6)

15

9000

External Fault 7 (EF7)

16

9000

External Fault 8 (EF8)

17

4140

Heatsink Fan (FAn)

Check drive cooling fan

18

7310

Overspeed Det (oS)

Check reference and reference gain
Check F1-08 and F1-09 settings

19

7310

Speed Deviation (dEv)

Check load, acc/dec times and system mechanics
Check F1-10 and F1-11 settings

1A

7301

PG Open (PGo)

Check PG card connections

1B

3130

Input Phase Loss (PF)

Excessive input voltage fluctuation

1C

3130

Output Phase Loss (LF)

Check for broken wire/loose terminals
Check motor rating

1D

5210

None

-

1E

5300

Operator Disconnected (oPr)

Reconnect the digital operator

Error Code

Description

Cause

Possible Solution