8 Output Assemblies (Drive Consumes)

YASKAWA ELECTRIC

SIEP C730600 43B 1000-Series Option SI-N3 Technical Manual

31

‹

Standard DI/DO Control (Vendor Specific Yaskawa Electric (YE) Assy) - 107 (0x6B)

Speed Reference

Speed Command
Sets drive speed reference
Unit depends on o1-03.
Unit is not affected by Speed Scale SS.

Output

Instance

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

107

0

Multi-

Function Input

8

Multi-

Function Input

7

Multi-

Function Input

6

Multi-

Function Input

5

Multi-

Function Input

4

Multi-

Function Input

3

Run

Rev

Run

Fwd

1

Fault

Reset

External

Fault

2

Multi-

Function

Photocoupler 2

Multi-

Function

Photocoupler 1

Multi-

Function

Digital Output

3

4

Analog Output 1 (Low Byte)

5

Analog Output 1 (High Byte)

6

Speed Reference (Low Byte)

7

Speed Reference (High Byte)

Parameter

Data

Run Fwd

Forward Run Command
0: Stop
1: Forward Run

Run Rev

Reverse Run Command
0: Stop
1: Reverse Run

Multi-Function Input 3

Terminal S3 Function Input
0: Terminal S3 Function (H1-03) OFF
1: Terminal S3 Function (H1-03) ON

Multi-Function Input 4

Terminal S4 Function Input
0: Terminal S4 Function (H1-04) OFF
1: Terminal S4 Function (H1-04) ON

Multi-Function Input 5

Terminal S5 Function Input
0: Terminal S5 Function (H1-05) OFF
1: Terminal S5 Function (H1-05) ON

Multi-Function Input 6

Terminal S6 Function Input
0: Terminal S6 Function (H1-06) OFF
1: Terminal S6 Function (H1-06) ON

Multi-Function Input 7

Terminal S7 Function Input
0: Terminal S7 Function (H1-07) OFF
1: Terminal S7 Function (H1-07) ON

Multi-Function Input 8

Terminal S8 Function Input
0: Terminal S8 Function (H1-08) OFF
1: Terminal S8 Function (H1-08) ON

External Fault

External Fault EF0
0: No External Fault (EF0)
1: External Fault (EF0)

Fault Reset

Fault Reset
0: No Fault Reset
1: Fault Reset

Multi-Function Digital Output

Terminal M1/M2
0: M1/M2 OFF
1: M1/M2 ON
This function is enabled only when H2-01 is set to F.

Parameter

Data