5 Installation Procedure

18

YASKAWA ELECTRIC SIEP C730600 43B 1000-Series Option SI-N3 Technical Manual

‹

Option Baud Rate

The option supports standard baud rates of 125 kbps, 250 kbps, and 500 kbps.

Table 5 Parameter F6-51 Baud Rate Setting

„

Auto Baud Rate Sensing (F6-51 = 4)

Setting parameter F6-51 to 4 enables automatic baud rate detection and allows the option to automatically determine the
baud rate of the DeviceNet network.

Note: Auto baud rate sensing is valid only when there is more than one node physically on the DeviceNet network segment. If the auto

baud rate sensing fails to detect the baud rate, the drive digital operator will display “bUS” and the option LEDs will be OFF
(NS) and solid green (MS).

‹

EDS Files

To facilitate network implementation, obtain an EDS file from one of the following websites depending on your region:

US: http://www.yaskawa.com

Europe: http://www.yaskawa.eu.com

Japan: http://www.e-mechatronics.com

Other areas: Contact your Yaskawa representative.

Description

Value

125 kbps

0

250 kbps

1

500 kbps

2

Programmable from Network

3

Auto Detect

4