6 Related Parameters

20

YASKAWA ELECTRIC SIEP C730600 43B 1000-Series Option SI-N3 Technical Manual

F6-55
(3C6)

DeviceNet Baud Rate
Monitor

(Read only) DeviceNet actual communication speed
0: 125 kbps
1: 250 kbps
2: 500 kbps
Note: Used in the DeviceNet Object

Default: 0
Range: 0 to 2

F6-56
(3D7)

DeviceNet Speed Scaling

Sets the scaling factor for the Speed Monitor in the DeviceNet Object Class 2A hex
Note: Used in the AC/DC Drive Object

Default: 0
Min: -15
Max: 15

F6-57
(3D8)

DeviceNet Current Scaling

Sets the scaling factor for the Output Current Monitor in the DeviceNet Object Class
2A hex
Note: Used in the AC/DC Drive Object

Default: 0
Min: -15
Max: 15

F6-58
(3D9)

DeviceNet Torque Scaling

Sets the scaling factor for the Torque Monitor in the DeviceNet Object Class 2A hex
Note: Used in the AC/DC Drive Object

Default: 0
Min: -15
Max: 15

F6-59

(3DA)

DeviceNet Power Scaling

Sets the scaling factor for the Power Monitor in the DeviceNet Object Class 2A hex
Note: Used in the AC/DC Drive Object

Default: 0
Min: -15
Max: 15

F6-60

(3DB)

DeviceNet Voltage Scaling

Sets the scaling factor for the Voltage Monitor in the DeviceNet Object Class 2A
Note: Used in the AC/DC Drive Object

Default: 0
Min: -15
Max: 15

F6-61

(3DC)

DeviceNet Time Scaling

Sets the scaling factor for the Time Monitor in the DeviceNet Object Class 2A hex
Note: Used in the AC/DC Drive Object

Default: 0
Min: -15
Max: 15

F6-62

(3DD)

DeviceNet Heartbeat
Interval

Sets the heartbeat interval
Note: Used in the Identity Object

Default: 0
Min: 0
Max: 10

F6-63

(3DE)

DeviceNet Network MAC
ID

(Read only) Actual MAC address
Note: Used in the DeviceNet Object

Default: 0
Min: 0
Max: 63

U6-98

(7F8)

Previous Option Fault

Displays previous faulted status.
0: No fault
1: Option failure
2: PLC in idle state
3: Force fault
1000: Network power loss
1001: Connection timeout
1002: Duplicate MAC ID
1003: Bus-off
Note: Used in DeviceNet Option Faults

Range: 0 to 3;
1000 to 1003

U6-99

(7F9)

Current Option Fault

Displays the most recent fault status.
0:No fault
1: Option failure
2: PLC in idle state
3: Force fault
1000: Network power loss
1001: Connection timeout
1002: Duplicate MAC ID
1003: Bus-off
Note: Used in DeviceNet Option Faults

Range: 0 to 3;
1000 to 1003

<1> To start and stop the drive with the DeviceNet master device using serial communications, set b1-02 to 3 or set the Net Control bit in the

assemblies or Control Supervisor Object. To control the frequency reference of the drive via the master device, set b1-01 to 3 or set the Net

Reference bit in the assemblies or AC/DC object.

<2> Setting F6-01 or F6-03 to 3 will allow the drive to continue to operate after detecting a fault. When allowing the drive to continue operation after

fault detection, be sure to take proper safety measures such as installing an emergency stop switch.

<3> Enabled in CLV, AOLV/PM, and CLV/PM control modes (A1-02 = 3, 6, or 7). When enabled, d5-01 determines whether the value is read as the

torque limit value (d5-01 = 0) or read as the torque reference value (d5-01 = 1). This value is read as the torque limit in CLV/PM.

<4> Default setting specifies that the torque reference or torque limit is to be provided via network communications (F6-06 = 1). The motor may not

rotate if no torque reference or torque limit is supplied from the PLC.

<5> All MAC addresses must be unique.

<6> Setting unavailable values will initialize Polled Consuming Assembly (PCA) and Polled Producing Assembly (PPA).

<7> Cycle power for setting changes to take effect.

No.

(Addr.

Hex)

Name

Description

Values