9 Input Assemblies (Drive Produces)

YASKAWA ELECTRIC

SIEP C730600 43B 1000-Series Option SI-N3 Technical Manual

41

‹

Speed and Torque Control Input - 72 (0x48)

Warning

Warning
0: No Warning Occurred
1: Warning Occurred

Running 1 (FWD)

Forward Running
0: Stop or Reverse Running
1: Forward Running

Running 2 (REV)

Reverse Running
0: Stop or Forward Running
1: Reverse Running

Ready

Drive Ready
0: Not Ready
1: Ready

Ctrl from Net

Status of Run command from Network
0: Run command is not from network
1: Run command is from network

Ref from Net

Status of Speed reference from Network
0: Speed reference is not from network
1: Speed reference is from network

At Speed

Speed Agree
0: No Speed Agree
1: Actual speed at speed reference

State

Drive Status
2: Processing
3: Ready (Stopped)
4: Awaiting Run command
5: Ramping to stop
6: Fault stop
7: Fault

Speed Actual

Actual Drive Speed
Monitors drive output frequency
Speed actual data: Output frequency

× 2

SS

(SS: Speed scale)

Range: 0 to 0xFFFF
For example, when output frequency of 4096 with a speed scale of 2
Speed actual data = 4096

×

2

2

= 16384 = 0x4000

Unit depends on o1-03.

Input

Instance

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

72

0

Running 1

(FWD)

Faulted

1

2

Speed Actual (Low Byte)

3

Speed Actual (High Byte)

4

Torque Actual (Low Byte)

5

Torque Actual (High Byte)

Name

Description

Faulted

Faulted
0: No Faults Occurred
1: Fault Occurred

Running 1

Forward Running
0: Stop or Reverse Running
1: Forward Running

Name

Description