8 Output Assemblies (Drive Consumes)

YASKAWA ELECTRIC

SIEP C730600 43B 1000-Series Option SI-N3 Technical Manual

25

‹

MEMOBUS/Modbus Message Command
(Vendor Specific Yaskawa Electric (YE) Assy) - 100 (0x64)

Note: This is a paired assembly (100/150).

Table 8 Function Code Decode Table

Note: Refer to the MEMOBUS/Modbus Data Table in the drive Technical Manual for a list of monitor data using the MEMOBUS/

Modbus message area.

Fault Reset

Fault Reset
0: No Fault Reset
1: Fault Reset

NetCtrl

Run command from Network
0: Depends on b1-02
1: Enables the run command from network

NetRef

Speed reference from Network
0: Depends on b1-01
1: Enables the speed reference from network

Speed Reference

Speed Command
Sets drive speed reference
Speed reference data:
Frequency reference × 2

SS

(SS: Speed scale)

Setting range: 0 to 0xFFFF
For example, when setting a reference of 1024 with a speed scale of 2
Speed reference data = 1024 × 2

2

= 4096 = 0x1000

Unit depends on o1-03.

Torque Reference/Torque Limit

Torque Reference/Torque Limit
Sets the torque reference and torque limit in units of 0.1%.
Sets the torque reference when using torque control (d5-01 = 1).
Sets the torque limit when using speed control (d5-01 = 0).
The torque reference and torque limit are disabled when F6-06 = 0.

Output Instance

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

100

0

Function Code

1

Register Number (High Byte)

2

Register Number (Low Byte)

3

Register Data (High Byte)

4

Register Data (Low Byte)

Name

Description

Function Code

MEMOBUS/Modbus Function Code

Refer to Function Code Decode Table on page 25

.

Register Number

MEMOBUS/Modbus Register Number

Register Data

MEMOBUS/Modbus Register Data

Function Code

MEMOBUS/Modbus Function

0x00

No Operation

0x03

Read Register

0x10

Write Register

Name

Description