9 Input Assemblies (Drive Produces)

YASKAWA ELECTRIC

SIEP C730600 43B 1000-Series Option SI-N3 Technical Manual

59

‹

Change of State Response (Vendor Specific Yaskawa Electric (YE) Assy) - 199
(0xC7)

0x22

Option generated busy event. The MEMOBUS/Modbus requested operation is in the process loop but the drive is not done yet.
Writing “Enter” when drive is running.
Attempt to write data that is read only.
Attempt to write a constant when drive is running.
During a CPF06 event attempting to write to registers other than A1-00 to A1-05, E1-03, o2-04.

0x23

Attempting to write during a drive undervoltage (Uv) event.

0x24

Attempting to write while the drive is storing data.

Input Instance Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

199

0

Multi-

Function

Input 4

Multi-Function

Input 3

NetCtrl

NetRef

Fault Reset

External

Fault

Run Rev

Run Fwd

1

Multi-

Function

Input 8

Multi-

Function

Input 7

Multi-

Function

Input 6

Multi-

Function

Input 5

2

FAULT

ALARM

READY

Speed Agree

Reset

REV

Running

ZSP

Running

3

NetCtrl

(Status)

NetRef

(Status)

2nd Motor

Uv

oPE

4

Output Frequency (Low Byte)

5

Output Frequency (High Byte)

6

Actual Torque (Low Byte)

7

Actual Torque (High Byte)

Parameter

Data

Run Fwd

Forward Run command from Network
0: Forward Run command is not from network
1: Forward Run command is from network

Run Rev

Reverse Run command from Network
0: Reverse Run command is not from network
1: Reverse Run command is from network

External Fault

External Fault command from Network
0: External Fault command is not from network
1: External Fault command is from network

Fault Reset

Fault Reset command from Network
0: Fault Reset command is not from network
1: Fault Reset command is from network

NetRef

Reference command from Network
0: Reference command is not from network
1: Reference command is from network

NetCtrl

Run command from Network
0: Run command is not from network
1: Run command is from network

Multi-Function Input 3

Terminal S3 command by Network
0: Terminal S3 command OFF
1: Terminal S3 command ON

Multi-Function Input 4

Terminal S4 command by Network
0: Terminal S4 command OFF
1: Terminal S4 command ON

Multi-Function Input 5

Terminal S5 command by Network
0: Terminal S5 command OFF
1: Terminal S5 command ON

Multi-Function Input 6

Terminal S6 command by Network
0: Terminal S6 command OFF
1: Terminal S6 command ON

Error Code

Description