12 Troubleshooting

76

YASKAWA ELECTRIC SIEP C730600 43B 1000-Series Option SI-N3 Technical Manual

„

DeviceNet Option Fault Monitors U6-98 and U6-99

The DeviceNet Option SI-N3 can declare the error/warning conditions via drive monitor parameters as shown in

Table 22

.

Table 22 DeviceNet Option Fault Monitor Descriptions

Two drive monitor parameters, U6-98 (OPTN LATCH STAT) and U6-99 (OPTN ACTIVE STAT), assist the user in
network troubleshooting.

• U6-98 displays the first declared fault since the last fault reset or power cycle.
• U6-99 displays the present DeviceNet Option SI-N3 status.

These parameters are accessible from the DeviceNet network the or the drive digital operator. A drive fault reset or
power off clears and refreshes both U6-98 and U6-99.

Note: In the event of a PLC idle state, the action taken by the DeviceNet Option SI-N3 depends upon the value of parameter F6-54

(Idle Mode Fault Detection).

‹

Automatic Device Replacement (ADR)

This DeviceNet Interface is compatible with the ADR feature associated with Rockwell controllers and DeviceNet
Scanners. ADR features Configuration Recovery and Auto Address Recovery.

„

Configuration Recovery (CR)

CR is the ability of the scanner to download previously uploaded and saved configuration data to the DeviceNet node.

When a DeviceNet node is removed and returned to the network or replaced with another device, an ADR-enabled
scanner reads the Electronic Key of the device that is configured in the scanner. A typical setup of the Electronic Key is:
Vendor ID, Product Code, Model Number and Product Revision. When the CR feature is enabled, the stored
configuration is downloaded to the DeviceNet node.

1F

6320

EEPROM R/W Error (Err)

Cycle drive power – Replace drive if fault continues

20

0000

None

21

7500

DeviceNet Comm Error (bUS)

Check DeviceNet network cable connections.
Check 24VDC power supply voltage.

22

Check DeviceNet Option Card installation and connections.

23

Cycle drive power – Replace DeviceNet Option or drive if fault continues.

24

25

8321

Out of Control (CF)

Check motor parameters
Auto-tune

27

9000

External Fault 0 (EF0)

Check PLC program
Check MI switch setting
Check DeviceNet Option Card LEDs for fault indication

<1> Drive error code is stored in MEMOBUS/Modbus address 0080 hex.

Fault Condition

Fault Declared Status Value (U6-99/

U6-98)

Description

No Fault

n/a

0

No faults.

CPU Error

EF0

1

Option board failure.

PLC in Idle State

EF0

2

PLC is sending polled I/O with all data set to zero.

Force Fault

EF0

3

Network sent a message to force this node to the fault state.

Network Power Loss

BUS ERROR

1000

Power on DeviceNet network is off.

Connection Time-out

BUS ERROR

1001

This nodes timer (Expect Packet Rate) timed out.

Dup MAC ID

BUS ERROR

1002

This node and at least one other node have the same MAC ID.
Another node sent its MAC ID to the network first.

Bus-Off

BUS ERROR

1003

CAN transceiver senses network error.

Drive Error

Code

(hex)

<1>

DeviceNet

Error Code

(hex)

Description

Corrective Action