8 Output Assemblies (Drive Consumes)

YASKAWA ELECTRIC

SIEP C730600 43B 1000-Series Option SI-N3 Technical Manual

35

‹

Speed Command 2 (Vendor Specific Yaskawa Electric (YE) Assy) - 122 (0x7A)

Fault Reset

Fault Reset
0: No Fault Reset
1: Fault Reset

Torque Reference/Torque Limit

Torque Reference/Torque Limit
Sets the torque reference and torque limit in units of 0.1%.
Sets the torque reference when using torque control (d5-01 = 1).
Sets the torque limit when using speed control (d5-01 = 0).
The torque reference and torque limit are disabled when F6-06 = 0.

Output Instance

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

122

0

Multi-

Function

Input 8

Multi-

Function

Input 7

Multi-

Function

Input 6

Multi-

Function

Input 5

Multi-

Function

Input 4

Multi-

Function

Input 3

Run
Rev

Run

Fwd

1

Fault

Reset

External

Fault

2

Speed Reference (Low Byte)

3

Speed Reference (High Byte)

4

NetRef

5

NetCtrl

Parameter

Data

Run Fwd

Forward Run Command
0: Stop
1: Forward Run

Run Rev

Reverse Run Command
0: Stop
1: Reverse Run

Multi-Function Input 3

Terminal S3 Function Input
0: Terminal S3 Function (H1-03) OFF
1: Terminal S3 Function (H1-03) ON

Multi-Function Input 4

Terminal S4 Function Input
0: Terminal S4 Function (H1-04) OFF
1: Terminal S4 Function (H1-04) ON

Multi-Function Input 5

Terminal S5 Function Input
0: Terminal S5 Function (H1-05) OFF
1: Terminal S5 Function (H1-05) ON

Multi-Function Input 6

Terminal S6 Function Input
0: Terminal S6 Function (H1-06) OFF
1: Terminal S6 Function (H1-06) ON

Multi-Function Input 7

Terminal S7 Function Input
0: Terminal S7 Function (H1-07) OFF
1: Terminal S7 Function (H1-07) ON

Multi-Function Input 8

Terminal S8 Function Input
0: Terminal S8 Function (H1-08) OFF
1: Terminal S8 Function (H1-08) ON

External Fault

External Fault EF0
0: No External Fault (EF0)
1: External Fault (EF0)

Fault Reset

Fault Reset
0: No Fault Reset
1: Fault Reset

Speed Reference

Speed Command
Sets drive speed reference
Unit depends on o1-03.
Unit is not affected by Speed Scale SS.

NetRef

Speed reference form Network
0x00: Depends on b1-01
0x01: Enables the speed reference from network

Parameter