12 Troubleshooting

YASKAWA ELECTRIC

SIEP C730600 43B 1000-Series Option SI-N3 Technical Manual

73

12

Troubleshooting

‹

Drive-Side Error Codes

Table 19

lists the various option-related fault codes. Refer to the drive Technical Manual for further information about

fault codes.

„

Faults

Both bUS (Option Communication Error) and EF0 (External Fault Input from the option) can appear as either an alarm
or as a fault. When a fault occurs, the digital operator ALM LED remains lit. When an alarm occurs, the digital operator
ALM LED flashes.

Check the following items first when an error code occurs on the drive:

• Communication cable connections
• Make sure the option is properly installed to the drive
• Operation status of the controller program and controller CPU
• Did a momentary power loss interrupt communications?

Table 19 Fault Displays, Causes, and Possible Solutions

Digital Operator Display

Fault Name

bUS

Option Communication Error
The connection was lost after establishing initial communication.
Only detected when the run command frequency reference is assigned to the option
(bl-01 = 3 or bl-02 = 3).

Cause

Possible Solution

Master controller (PLC) has stopped
communicating

Check for faulty wiring.
Correct any wiring problems.

Communication cable is not connected properly

A data error occurred due to noise

• Counteract noise in the control circuit wiring, main circuit lines, and ground wiring.
• If a magnetic contactor is the noise source, install a surge absorber to the contactor coil.
• Use cables recommended by Yaskawa or another type of shielded line.

Ground the shield on the controller side and on the option side.

Option is damaged

If there are no wiring problems and the fault continues to occur, replace the option.

Network power loss

The power on the DeviceNet network cable is 0.
Verify power is available between option terminals V+ (red) and V- (black).

Connection timeout

The option Expected Packet Rate (EPR) timer timed out.
Make sure that EPR time is set properly.

Duplicate MAC ID

The option MAC ID and at least one other node have the same MAC ID.
Verify F6-50 is set properly.

Digital Operator Display

Fault Name

EF0

External Fault Input from the option
The alarm function for an external device has been triggered.

Cause

Possible Solution

An external fault is being sent from the main
controller (PLC)

• Remove the cause of the external fault
• Reset the external fault input from the PLC device

Problem with the PLC program

Check the program used by the PLC and make the appropriate corrections.

Digital Operator Display

Fault Name

oFA00

Non-Compatible Option connected to drive port CN5-A
Option is not properly connected.

Cause

Possible Solution

Non-compatible option connected to drive port
CN5-A

Use only compatible options. Connect the SI-N3 to CN5-A. For other option connections refer
to the Installation Manual for those options.

Digital Operator Display

Fault Name

oFA01

Option Fault (CN5-A)
Option is not properly connected.

Cause

Possible Solution

Problem with the connector between the drive and
option

Turn the power off and check the connectors between the drive and option.