beautypg.com

Table 5.6, Status flags (registers 30010 and 30011), Table 5.7 – RLE LD5200 V.2.3 User Manual

Page 98: Status flags (register 30013 - 30273)

background image

98

LD5200 User Guide

800.518.1519

5

Modbus Communication

Status Flags

30269

Modbus Zone126 Distance

Location of leak

Ft/Meters

0-65535

30270

Modbus Zone127 Status

Bit Level Status

None

0-65535

30271

Modbus Zone127 Distance

Location of leak

Ft/Meters

0-65535

30272

Modbus Zone128 Status

Bit Level Status

None

0-65535

30273

Modbus Zone128 Distance

Location of leak

Ft/Meters

0-65535

Register

Name

Description

Units

Range

Table 5.5

Input Registers (continued)

Register 30010

Register 30011

Bit

Description

Bit

Description

00

1 = Zone1

00

1 = Zone17

01

1 = Zone2

01

1 = Zone18

02

1 = Zone3

02

1 = Zone19

03

1 = Zone4

03

1 = Zone20

04

1 = Zone5

04

1 = Zone21

05

1 = Zone6

05

1 = Zone22

06

1 = Zone7

06

1 = Zone23

07

1 = Zone8

07

1 = Zone24

08

1 = Zone9

08

1 = Zone25

09

1 = Zone10

09

1 = Zone26

10

1 = Zone11

10

1 = Zone27

11

1 = Zone12

11

1 = Zone28

12

1 = Zone13

12

1 = Zone29

13

1 = Zone14

13

1 = Zone30

14

1 = Zone15

14

1 = Zone31

15

1 = Zone16

15

1 = Zone32

Table 5.6

Status Flags (Registers 30010 and 30011)

Bit

Description

00

1= Leak Detected

01

1 = Cable Break

02

1 = Contamination

07

1 = Communication Loss

Table 5.7

Status Flags (Register 30013 - 30273)