Table 5.6, Status flags (registers 30010 and 30011), Table 5.7 – RLE LD5200 V.2.3 User Manual
Page 98: Status flags (register 30013 - 30273)
![background image](https://www.manualsdir.com/files/802966/content/doc098.png)
98
LD5200 User Guide
800.518.1519
5
Modbus Communication
Status Flags
30269
Modbus Zone126 Distance
Location of leak
Ft/Meters
0-65535
30270
Modbus Zone127 Status
Bit Level Status
None
0-65535
30271
Modbus Zone127 Distance
Location of leak
Ft/Meters
0-65535
30272
Modbus Zone128 Status
Bit Level Status
None
0-65535
30273
Modbus Zone128 Distance
Location of leak
Ft/Meters
0-65535
Register
Name
Description
Units
Range
Table 5.5
Input Registers (continued)
Register 30010
Register 30011
Bit
Description
Bit
Description
00
1 = Zone1
00
1 = Zone17
01
1 = Zone2
01
1 = Zone18
02
1 = Zone3
02
1 = Zone19
03
1 = Zone4
03
1 = Zone20
04
1 = Zone5
04
1 = Zone21
05
1 = Zone6
05
1 = Zone22
06
1 = Zone7
06
1 = Zone23
07
1 = Zone8
07
1 = Zone24
08
1 = Zone9
08
1 = Zone25
09
1 = Zone10
09
1 = Zone26
10
1 = Zone11
10
1 = Zone27
11
1 = Zone12
11
1 = Zone28
12
1 = Zone13
12
1 = Zone29
13
1 = Zone14
13
1 = Zone30
14
1 = Zone15
14
1 = Zone31
15
1 = Zone16
15
1 = Zone32
Table 5.6
Status Flags (Registers 30010 and 30011)
Bit
Description
00
1= Leak Detected
01
1 = Cable Break
02
1 = Contamination
07
1 = Communication Loss
Table 5.7
Status Flags (Register 30013 - 30273)