Eia-232 interface, B.1 set the ip address through the eia-232 port, Set the ip address through the eia-232 port – RLE LD5200 V.2.3 User Manual
Page 103: Eia-232 i, Nterface
rletech.com
LD5200 User Guide
103
A
P P E N D I X
C
HAPTER
0
EIA-232 I
NTERFACE
The EIA-232 Interface is used primarily for advanced diagnostic and configuration.
The Bootloader section is designed for experienced technicians or users
responsible for maintaining the system. EXIT IMMEDIATELY if you are not
trained in the use of the Bootloader commands.
Contact the manufacturer for more information regarding the commands in this
section.
B.1
Set the IP Address through the EIA-232 Port
1
Connect the EIA-232 port (P1) on the LD5200 to a terminal or PC running terminal
emulation software (HyperTerminal) with a 9-pin male-female straight through serial cable.
2
2. Set the appropriate communication port to 9600 baud, NO parity, 8 data bits, 1 stop
bit, (9600/N/8/1), and no software or hardware flow command.
3
Once the terminal emulation software starts, type
?
and press Enter on the keyboard and the
Main Menu should appear. If the Main Menu does not appear, check the communication
settings and make sure the unit is powered on.
4
From the Main Menu type netcfg to select the Network Configuration Menu.
♦
Enter the new IP address for the LD5200 by typing
ip xxx.xxx.xxx.xxx
, where
xxx.xxx.xxx.xxx
is the new IP address of the unit. Separate each field with a decimal
point. For example, type
ip 10.0.0.50
.
♦
The LD5200 erases a memory block and copies data to flash memory before rebooting.
♦
The LD5200 IP address is now set and the LD5200 can be accessed through a Web
browser using the new IP address.
W
ARNING