4
Web Interface
Select Snmp Trap
Type
Select the appropriate trap type from the drop-down menu. SNMP
V3 is available as a separate LD5200 firmware package. The
distribution of SNMP V3 has geographic restrictions. Contact the
manufacturer for further information regarding SNMP V3.
V1 - Trap
V2C - Trap
V2C - Inform
V3 - Trap (not available on standard unit)
V3 - Inform (not available on standard unit)
Default setting: V1 -Trap
Max Inform Retries
The number of times the LD5200 will attempt to resend an
undelivered trap. Enter a number 0 - 999. Enter 0 for an unlimited
number of attempts.
Default setting: 0 (unlimited)
Inform Interval
The number of minutes that passes between inform operations.
Enter a number of minutes 1 - 999
Default setting: 1
Modbus Zone Traps
Enable or disable this function.
Default setting: Disable
V1/V2C Community Names
Get/Read
Default setting: public
Set/Write
Default setting: public
Trap
Default setting: public
Trap Communities
1 IP Address
Identify devices that receive Traps and/or Syslog messages from the
LD5200 and communicate with the LD5200 over the network.
Enter the receiving device’s IP address. Check the appropriate
boxes to designate whether the device will receive Traps and/or
Syslog messages.
2 IP Address
3 IP Address
4 IP Address
Send Test Trap -
Leak Detected
Send Test Trap -
Cable Break
Send Test Trap -
Contamination
Use these buttons to send test traps - test your system setup to
ensure all information has been entered correctly.
Option
Description
Table 4.11