13 eia-485 port/modbus/n2, Eia-485 port/modbus/n2, Table 4.12 – RLE LD5200 V.2.3 User Manual

Page 76: Modbus/eia-485 options

background image

76

LD5200 User Guide

800.518.1519

4

Web Interface

4.3.13 EIA-485 Port/Modbus/N2

If the LD5200 will communicate via the EIA-485 port, configure the necessary options here.

Figure 4.30

Modbus EIA-485 Page

Option

Description

Modbus/TCP/UDP

Slave Unit Identifier

This designator is used for Modbus RTU over an Ethernet

connection.

Set the slave unit identifier, 1-254. 0 = disabled.

Enable Alarm Relay

for Modbus Slaves

Enable or disable this option

Default setting: Disabled

EIA-485 Port 1

Function

Select Modbus-Slave or Modbus-Master

EIA-485 Port 1 Baud

Rate

Selectable: 9600, 19200, or 38400

EIA-485 Port 1 Slave

Address

Set the slave address, 1-254. 0 = disabled

EIA-485 Port 2

Function

Select Modbus Slave, Bacnet-MS/TP-Slave, Modbus-Master, or N2

(fixed, 9600, 8, n, 1)

EIA-485 Port 2 Baud

Rate

Selectable: 9600, 19200, or 38400

Table 4.12

Modbus/EIA-485 Options