1 leak settings, Leak settings, Table 3.10 – RLE LD5200 V.2.3 User Manual
Page 37: Lcd leak settings - configurable options, Leak settings” on, Or the we
![background image](https://www.manualsdir.com/files/802966/content/doc037.png)
rletech.com
LD5200 User Guide
37
3
LCD Touch Screen Interface
3.5.1 Leak
Settings
Leak Settings allows you to fine tune
the leak detection options available
on the LD5200. Use the Up, Down,
Select and Return buttons to
navigate through the leak settings
menu.
Option
Description
Leak Trip Point
The threshold for the amount of water required to trigger a leak
alarm. Adjust this number to adjust the sensitivity of the leak
alarm.
A lower number yields a more sensitive system, so the system
will trigger a leak alarm with less water present.
A higher number produces a less sensitive system, so more
water is required to trigger an alarm.
Enter a value between 25 and 175 microamps.
Default setting: 150uA.
Contamination Trip
Point
The threshold for the amount of contamination required to
trigger a cable contamination alarm. Adjust this number to
adjust the sensitivity of the contamination alarm.
A lower number yields a more sensitive system, so the system
will trigger a contamination alarm with less contamination
present.
A higher number produces a less sensitive system, so more
contamination is required to trigger an alarm.
Enter a value between 20 and 175 microamps.
Default setting: 50uA.
Leak Alarm Delay
The amount of time that passes between the time a leak is
detected and the annunciation of the leak alarm. The leak trip
point must be exceeded for the duration of this delay.
Enter a value between 5 and 990 seconds.
Default setting: 20 seconds
Table 3.10
LCD Leak Settings - Configurable Options
LCD - Leak Settings