3.5.1 Leak

Settings

Leak Settings allows you to fine tune

the leak detection options available

on the LD5200. Use the Up, Down,

Select and Return buttons to

navigate through the leak settings

menu.

Option

Description

Leak Trip Point

The threshold for the amount of water required to trigger a leak

alarm. Adjust this number to adjust the sensitivity of the leak

alarm.
A lower number yields a more sensitive system, so the system

will trigger a leak alarm with less water present.
A higher number produces a less sensitive system, so more

water is required to trigger an alarm.

Enter a value between 25 and 175 microamps.

Default setting: 150uA.

Contamination Trip

Point

The threshold for the amount of contamination required to

trigger a cable contamination alarm. Adjust this number to

adjust the sensitivity of the contamination alarm.

A lower number yields a more sensitive system, so the system

will trigger a contamination alarm with less contamination

present.
A higher number produces a less sensitive system, so more

contamination is required to trigger an alarm.

Enter a value between 20 and 175 microamps.

Default setting: 50uA.

Leak Alarm Delay

The amount of time that passes between the time a leak is

detected and the annunciation of the leak alarm. The leak trip

point must be exceeded for the duration of this delay.

Enter a value between 5 and 990 seconds.

Default setting: 20 seconds

Table 3.10

LCD Leak Settings - Configurable Options

LCD - Leak Settings