5 apply power to the ld5200, Apply power to the ld5200, Figure 2.5 – RLE LD5200 V.2.3 User Manual
Page 22: Secure the cable
22
LD5200 User Guide
800.518.1519
2
Installation
♦
The J-clip’s adhesive backing does not work well on porous concrete floors. RLE
recommends using a drop of silicone or another nonconductive adhesive to help secure the
J-clip to the floor.
IMPORTANT
Do not install the cable directly in front of an air conditioner. Allow a minimum of 4 to 6 feet
(1.22 to 1.83m) between the unit and the cable. If the cable is too close to the air conditioning
unit’s air stream, the moisture from the humidifier may cause false leak readings. If the cable
must be installed in front of an air conditioning unit, place the J-clips 3 feet (0.91m) apart.
.
Figure 2.5
Secure the Cable
2.5
Apply Power to the LD5200
A dedicated circuit breaker must be provided within close proximity to the LD5200
and be clearly marked as the disconnecting device for the LD5200 leak detection
controller.
Do not connect 120/230 VAC directly to the unit, or damage will occur to the
circuitry.
Make sure the dedicated circuit breaker is in the off position before connecting the
AC power wires to the LD5200.
1
Engage a certified electrician to run a power supply and necessary conduit to the location of
the LD5200.
2
Remove any necessary knock-outs from the bottom of the enclosure, and route the power
supply into the enclosure, to the power input terminal block. Insert the wires as noted on the
enclosure’s backplate: Neutral - Line - Ground. Ensure all connections are correct and all
screw terminals are tightened and secure.
3
Apply power to the LD5200. The device will boot (initialize).