Table 4.1, Leak configuration options – RLE LD5200 V.2.3 User Manual
Page 51
![background image](https://www.manualsdir.com/files/802966/content/doc051.png)
rletech.com
LD5200 User Guide
51
4
Web Interface
Option
Description
Leak Trip Point
The threshold for the amount of water required to trigger a leak
alarm. Adjust this number to adjust the sensitivity of the leak alarm.
A lower number yields a more sensitive system, so the system will
trigger a leak alarm with less water present.
A higher number produces a less sensitive system, so more water
is required to trigger an alarm.
Enter a value between 25 and 175 microamps.
Default setting: 150uA.
Contamination Trip
Point
The threshold for the amount of contamination required to trigger a
cable contamination alarm. Adjust this number to adjust the
sensitivity of the contamination alarm.
A lower number yields a more sensitive system, so the system will
trigger a contamination alarm with less contamination present.
A higher number produces a less sensitive system, so more
contamination is required to trigger an alarm.
Enter a value between 20 and 175 microamps.
Default setting: 50uA.
Leak Alarm Delay
The amount of time that passes between the time a leak is detected
and the annunciation of the leak alarm.
The leak trip point must be exceeded for the duration of this delay.
Default setting: 20 seconds
Contamination
Alarm Delay
The amount of time that passes between the time a contamination
is detected and the annunciation of the contamination alarm.
The contamination trip point must be exceeded for the duration of
this delay.
Default setting: 40 seconds
Table 4.1
Leak Configuration Options