Leak Trip Point

The threshold for the amount of water required to trigger a leak

alarm. Adjust this number to adjust the sensitivity of the leak alarm.

A lower number yields a more sensitive system, so the system will

trigger a leak alarm with less water present.
A higher number produces a less sensitive system, so more water

is required to trigger an alarm.

Enter a value between 25 and 175 microamps.

Default setting: 150uA.

Contamination Trip

Point

The threshold for the amount of contamination required to trigger a

cable contamination alarm. Adjust this number to adjust the

sensitivity of the contamination alarm.

A lower number yields a more sensitive system, so the system will

trigger a contamination alarm with less contamination present.
A higher number produces a less sensitive system, so more

contamination is required to trigger an alarm.

Enter a value between 20 and 175 microamps.

Default setting: 50uA.

Leak Alarm Delay

The amount of time that passes between the time a leak is detected

and the annunciation of the leak alarm.

The leak trip point must be exceeded for the duration of this delay.

Default setting: 20 seconds

Contamination

Alarm Delay

The amount of time that passes between the time a contamination

is detected and the annunciation of the contamination alarm.

The contamination trip point must be exceeded for the duration of

this delay.

Default setting: 40 seconds

Table 4.1

Leak Configuration Options