3.5.8 Bacnet
The LD5200 can communicate via
BACnet. BACnet allows building
automation and control devices to
communicate, regardless of the
building services they perform.
Use this screen to configure BACnet
options.
3.5.9 Clear
History
Select this option to clear the Alarm History and Trend Logs.
Option
Description
Device Name
Designate a unique name for the LD5200, up to 30 characters.
Device ID
Set the device ID, up to 30 characters. 0 = disabled.
Description
Enter a description for the device, up to 30 characters.
UDP Port
Enter a 0 to specify port 47808 (0xBAC0) as the UDP port. If
another port value is specified by your application, enter that
value here.
Default setting: 0
Ms/Tp Max Master
Represents the number of devices on the EIA-485 string.
Commonly, the Max Master is set to the same setting as the
BACnet master.
Table 3.17
LCD Bacnet Setup - Configurable Options