3

LCD Touch Screen Interface

3.5.8 Bacnet

The LD5200 can communicate via

BACnet. BACnet allows building

automation and control devices to

communicate, regardless of the

building services they perform.

Use this screen to configure BACnet

options.

3.5.9 Clear

History

Select this option to clear the Alarm History and Trend Logs.

Option

Description

Device Name

Designate a unique name for the LD5200, up to 30 characters.

Device ID

Set the device ID, up to 30 characters. 0 = disabled.

Description

Enter a description for the device, up to 30 characters.

UDP Port

Enter a 0 to specify port 47808 (0xBAC0) as the UDP port. If

another port value is specified by your application, enter that

value here.

Default setting: 0

Ms/Tp Max Master

Represents the number of devices on the EIA-485 string.

Commonly, the Max Master is set to the same setting as the

BACnet master.

Table 3.17

LCD Bacnet Setup - Configurable Options

LCD - Bacnet Setup Menu