Table 4.13, Bacnet options – RLE LD5200 V.2.3 User Manual
Page 79
rletech.com
LD5200 User Guide
79
4
Web Interface
Figure 4.31
Bacnet Page
Option
Description
BACnet Device
Name
Designate a unique name for the LD5200, up to 30 characters
BACnet Device ID
Set the device ID, up to 30 characters. 0 = disabled
BACnet Description
Enter a description for the device, up to 30 characters
Bacnet UDP Port
Enter a 0 to specify port 47808 (0xBAC0) as the UDP port. If another
port is specified by your application, enter that value here.
Default setting: 0
Bacnet MS/TP Max
Master
Set the slave address, 1-127. 0 = Slave only
Default setting: 0
Register as Foreign
Device at IP
IP address of the master device with which you’re trying to
communicate. Requires a BBMD for foreign device discovery.
Registration Time-
to-Live
Time, in seconds, for foreign device discovery.
Foreign Device
Table #1 & #2
Fixed fields whose content is drawn from the entries in the Register
Foreign Device and Registration T-t-L fields.
Bacnet BBMD-BDT
Used by some BACnet masters for discovery on different subnets.
LD5200 IP Address
Non-editable, this address is configured through the Network/IP link.
(Primary) #1 IP
Address
Designate the appropriate IP addresses.
#2 IP Address
#3 IP Address
#4 IP Address
Bacnet Alarms Event Notification
Recipient #1 IP
Address
When there is a BACnet alarm, a message will be sent to this
address.
Notification Type
Select unconfirmed or confirmed. If you select confirmed, the
recipient will be required to acknowledge the alarm.
Default setting: Unconfirmed
Notification Class
A list of devices to be informed if an event enrollment object
determines that a warning or alarm message needs to be sent.
Priority
Designate a priority to controls where conflicting control situations
may occur.
Leak Detected
Alarms
Select analog or binary
APDU_Timeout
Amount of time (milliseconds) between retransmissions of an APDU
requiring acknowledgement for which no acknowledgement has
been received.
Table 4.13
Bacnet Options