2 virtual zone, Virtual zone, Table 3.11 – RLE LD5200 V.2.3 User Manual

Page 40: Lcd virtual zone settings - configurable options

background image

40

LD5200 User Guide

800.518.1519

3

LCD Touch Screen Interface

3.5.2 Virtual

Zone

A virtual zone is a labeled reference point in a leak detection system. A virtual zone can consist

of a room, a drip pan containing a spot detector under an air handler unit, a combination of

rooms and components, or any other defined area whose identification would help in the

location of leaks.

The LD5200 allows you to establish

up to 32 virtual leak detection zones.

Dividing a leak detection system into

zones helps locate leaks quickly. It

simplifies troubleshooting by

allowing you to isolate different

sections of cable as separately

defined areas. Use the Virtual Zone

Settings page to configure the

LD5200’s virtual zones

Use the Up, Down, Select and Return

buttons to navigate through the

virtual zone menus.

Push the Select button to choose the blue highlighted zone you wish to configure or edit. Use

the LCD keyboard to give the zone a descriptive identifier. Push the Return button and log the

end distance for that particular virtual zone. To delete a virtual zone, select the zone and delete

the text from all fields.

Option

Description

#

A fixed number, 1 - 32, used to designate the Zone.

Label

A descriptive label for the zone, 30 characters or less.

End Distance

Record the sensing cable’s distance measurement at the END

of the zone.

Zone 1 starts at 0 feet / meters, and you designate the end

point for Zone 1. Zone 2 starts at zone 1’s ending distance; you

designate where Zone 2 ends. Each subsequent zone begins

where the previous zone ends.

Table 3.11

LCD Virtual Zone Settings - Configurable Options

LCD - Virtual Zone Settings Menu