2 virtual zone, Virtual zone, Figure 4.6 – RLE LD5200 V.2.3 User Manual
Page 54: Table 4.2, Virtual zone configuration options
![background image](https://www.manualsdir.com/files/802966/content/doc054.png)
54
LD5200 User Guide
800.518.1519
4
Web Interface
4.3.2 Virtual
Zone
A virtual zone is a labeled reference point in a leak detection system. A virtual zone can
consist of a room, a drip pan containing a spot detector under an air handler unit, a
combination of rooms and components, or any other defined area whose identification would
help in the location of leaks.
The LD5200 supports up to 32 virtual zones. Dividing a leak detection system into zones helps
locate leaks quickly. It simplifies troubleshooting by allowing you to isolate different sections
of cable as separately defined areas.
Figure 4.6
Virtual Zone Configuration Page
Option
Description
Zone #
A fixed number, 1 - 32, used to designate the Zone.
Label
Type a descriptive label for the zone, 30 characters or less.
End Distance
Record the sensing cable’s distance measurement at the END of
the zone.
Zone 1 starts at 0 feet / meters, and then you designate the end
point for Zone 1. Zone 2 starts at zone 1’s ending distance; you
designate where Zone 2 ends. Each subsequent zone begins
where the previous zone ends.
Table 4.2
Virtual Zone Configuration Options